Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

6. Contact materials including marking materials and pens, temperature indicating crayons,<br />

adhesive backed tape, cutting fluids, lubricants and cleaning fluids may be used only under<br />

the following limits:<br />

a. The total halogen content shall not exceed 200 parts per million (PPM).<br />

b. The total sulfur content shall not exceed 400 PPM.<br />

c. No intentionally added low melting point metals such as lead, zinc, copper, tin, antimony<br />

or mercury.<br />

d. Weld anti-spatter compounds shall not contain chlorine, fluorine, sulfur, mercury or<br />

other low melting point metals.<br />

e. Material and residue shall be completely removed when no longer required. Cleaning<br />

materials may be non-halogenated solvents or potable water containing no more than<br />

50 PPM chlorides. Contact materials shall be controlled and documented in accordance<br />

with the Contractors inspection and test plan as approved by the Buyer.<br />

7. Materials shall be certified by Certificate of Conformance for stainless steel use.<br />

3.2 <strong>IN</strong>STALLATION<br />

A. General - Comply with ASME B31.3, Process Piping Code, for Normal Service.<br />

B. Drawing plans, schematics, and diagrams indicate general location and arrangement of Nitrogen<br />

Gas Piping. Indicated locations and arrangements were used to size pipe and calculate friction<br />

loss, expansion, and other design considerations. Install piping as indicated unless deviations to<br />

layout are approved on Coordination Drawings.<br />

C. Install piping as indicated at right angles or parallel to building walls. Diagonal runs are<br />

prohibited unless specifically indicated otherwise. Route piping in orderly manner and maintain<br />

gradient. (Slope piping and provide drain valves at low points.)<br />

D. Pipes shall be designed with provisions for draining as shown on the drawings. Slope piping and<br />

provide drain valves at low points. Self draining configurations shall be employed to the extent<br />

practical.<br />

E. Mismatched bore diameter connections shall be prepared in accordance with ASME B31.3<br />

Figure 328.4.3(a). The trimmed bore shall not be less than the thickness of the thinner walled<br />

pipe. Misaligned pipe limitation shall be in accordance with the code. However bore trimming<br />

to correct piping misalignment is not permitted.<br />

F. Weld piping and attachments to pressure retaining components in accordance with ASME<br />

B31.3, Process Piping Code, for Normal Service.<br />

Contract 44577 KW Annex – Rev E. 44577-CSI-SPEC-001 402319-21