Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

Hardware Points Software Points<br />

Point Name AI AO BI BO AV BV Sched Trend Alarm<br />

Heat Pump Water Pump Failure ×<br />

Heat Pump Water Pump Running<br />

in Hand<br />

Heat Pump Water Pump Runtime<br />

Exceeded<br />

Heat Pump Chiller Failure ×<br />

Heat Pump Chiller Running in<br />

Hand<br />

Heat Pump Chiller Runtime Exceeded<br />

High Chilled Water Supply Temp ×<br />

Low Chilled Water Supply Temp ×<br />

High Heating Water Supply Temp ×<br />

Low Heating Water Supply Temp ×<br />

1.11 ECRT-BLR-501<br />

Show On<br />

Graphic<br />

Totals 2 0 2 2 0 0 0 4 10 6<br />

Total Hardware ( 6 ) Total Software ( 14 )<br />

A. Boiler System Run Conditions:<br />

1. The boiler system shall be enabled to run whenever:<br />

a. The heating water supply temperature is less than 115°F<br />

b. A definable number of zone temperatures are below the heating setpoint.<br />

c. AND outside air temperature is less than 40°F (adj.).<br />

2. To prevent short cycling, the boiler system shall run for and be off for minimum<br />

adjustable times (both user definable), unless shutdown on safeties or outside air<br />

conditions.<br />

3. The boiler shall run subject to its own internal safeties and controls.<br />

B. Boiler Safeties:<br />

1. The following safeties shall be monitored:<br />

a. Boiler alarm.<br />

b. Low Water Level.<br />

C. Alarms shall be provided as follows:<br />

1. Boiler alarm.<br />

2. Low Water Level alarm.<br />

D. Circulation Pump (ECRT-P-503):<br />

1. The circulation pump shall run anytime the boiler is called to run and shall have a user<br />

definable (adj.) delay on stop.<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 230993 - 15<br />

×<br />

×<br />

×<br />

×