Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

Design Pressure 50 psig<br />

Test Pressure 75 psig<br />

Operating Temperature<br />

Inspection and Test<br />

Method<br />

PIP<strong>IN</strong>G CODE: P-3 Fire Water Drain Piping (Force Main)<br />

Sizes 8” Pipe and Smaller<br />

Tubing/Pipe<br />

Fittings<br />

Environmental Extremes: -27°F to 110°F<br />

Normal Operating Extremes: 30°F to 80°F (Note 1)<br />

Visual Examination<br />

Hydrostatic testing at 150% of Design Pressure for all tubing and piping<br />

Steel Pipe, ASTM A 53/A 53M, Type S, Grade B, black or hot-dip zinc<br />

coated with ends matching joining method.<br />

Malleable-Iron Fittings: ASME B16.3, Class 150, threaded, ASTM A-105,<br />

Class WP carbon steel.<br />

Malleable-Iron Unions: ASME B16.39, Class 150, threaded, ASTM A-105,<br />

Class WP carbon steel.<br />

Steel Flanges: ASME B16.5, Class 150, ASTM A-105 carbon steel.<br />

Wrought-Steel Butt-Welding Fittings: ASME B16.9, Schedule 40, ASTM<br />

A-234, Class WPB carbon steel.<br />

Valves As called out in Specification Section 221413<br />

Note:<br />

1) Based on 30°F winter and 80°F summer approximate ground temperatures.<br />

2) Standards referenced above shall be used unless approved by buyer.<br />

END OF <strong>SECTION</strong> 221413<br />