Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

1.4 QUALITY ASSURANCE<br />

A. Testing Agency Qualifications: An independent agency, with the experience and capability to<br />

conduct the testing indicated, that is a member company of the InterNational Electrical Testing<br />

Association or is a nationally recognized testing laboratory (NRTL) as defined by OSHA in<br />

29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.<br />

1. Testing Agency's Field Supervisor: Person currently certified by the InterNational<br />

Electrical Testing Association to supervise on-site testing specified in Part 3.<br />

B. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70,<br />

Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for<br />

intended use.<br />

C. Comply with UL 467 for grounding and bonding materials and equipment.<br />

PART 2 - PRODUCTS<br />

2.1 CONDUCTORS<br />

A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by<br />

applicable Code or authorities having jurisdiction.<br />

B. Bare Copper Conductors:<br />

1. Solid Conductors: ASTM B 3.<br />

2. Stranded Conductors: ASTM B 8.<br />

3. Tinned Conductors: ASTM B 33.<br />

4. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch in diameter.<br />

5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.<br />

6. Bonding Jumper: Copper tape, braided conductors, terminated with copper ferrules; 1-<br />

5/8 inches wide and 1/16 inch thick.<br />

7. Tinned Bonding Jumper: Tinned-copper tape, braided conductors, terminated with<br />

copper ferrules; 1-5/8 inches wide and 1/16 inch thick.<br />

C. Grounding Bus: Rectangular bars of annealed copper, 1/4 by 2 inches in cross section, unless<br />

otherwise indicated; with insulators.<br />

2.2 CONNECTORS<br />

A. Listed and labeled by a nationally recognized testing laboratory acceptable to authorities having<br />

jurisdiction for applications in which used, and for specific types, sizes, and combinations of<br />

conductors and other items connected.<br />

B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, bolted pressure-type,<br />

with at least two bolts.<br />

1. Pipe Connectors: Clamp type, sized for pipe.<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 260526 - 2