Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

1.10 DELIVERY, STORAGE AND HANDL<strong>IN</strong>G<br />

A. See Section 016600, Material and Equipment Storage, and Handling, for general delivery storage<br />

and handling requirements.<br />

B. Individual compressed air components that are delivered to the fabrication site shall be cleaned<br />

in accordance with Part 3.1.A and capped with chloride/halogen free plastic caps.<br />

C. Compressed air components shall be labeled with the full fill line numbers in accordance with<br />

Section 220553, Identification for Plumbing Piping and Equipment.<br />

1.11 WARRANTY<br />

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or<br />

replace components of air compressor or air dryer equipment that fails in materials or<br />

workmanship within specified period.<br />

1. Compressor or Air Dryer Warranty Period: Five years from date of Substantial<br />

Completion.<br />

PART 2 - PRODUCTS<br />

2.1 GENERAL REQUIREMENTS FOR PACKAGED AIR COMPRESSOR, RECEIVER TANKS<br />

AND DESICCANT DRYER<br />

A. General Description Compressor Skid: Factory-assembled, -wired, -piped, and -tested; electricmotor-driven;<br />

air-cooled; continuous-duty single stage lubricated rotary screw air compressor,<br />

oil separator, water separator and compressor mounted wet air receiver tank that delivers air of<br />

quality equal to intake air.<br />

B. General Description Heated Purge Desiccant Dryer: Factory-assembled, -wired, -piped, and -<br />

tested; electric-motor-driven blower with heater; that deliver air of quality equal to or less than<br />

-40 deg F dew point air.<br />

C. General Description Air Receiver: Steel tank constructed according to ASME Boiler and<br />

Pressure Vessel Code: Section VIII, Division 1.<br />

1. Pressure Rating: At least as high as highest discharge pressure of connected compressor,<br />

and bearing appropriate code symbols.<br />

2. Interior Finish: Corrosion-resistant coating.<br />

3. Accessories: Include safety valve, pressure gage, electric automatic drain and manual<br />

isolation valve.<br />

D. General Description Mounting Frames: Fabricate mounting and attachment to compressor skid,<br />

receiver and desiccant dryer skid with reinforcement strong enough to resist packaged<br />

equipment movement during a seismic event when base is anchored to building structure.<br />

E. General Description Electrical Termination Panels: Comply with NEMA ICS 2 and UL 508<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221519 - 4