Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

O. Verify adhesive compatibility, if used.<br />

P. Verify Installation of all bolts.<br />

Q. Torque wrench and multiplier calibration.<br />

R. Torque bolts in star pattern, three passes.<br />

S. Verify bolt torque.<br />

T. Verify full engagement of nut (bolt threads at least flush with top on nut).<br />

3.9 LEAK TEST<strong>IN</strong>G<br />

A. Hydrostatic Leak Test:<br />

1. Test boundaries, valve alignment and closure.<br />

2. Joints visible.<br />

3. Pressure control and overpressure protection of test.<br />

4. System relief devices isolated.<br />

5. Water cleanliness and chemistry (ppm chloride limit on stainless).<br />

6. Hydrotest pressure, considering changes in elevation.<br />

7. Supports completed.<br />

8. Temporary supports where necessary (hydro of steam or gas lines).<br />

9. Variable springs constrained.<br />

10. Expansion joints constrained.<br />

11. Verification of pressure rating of components.<br />

12. Use of strainers to protect equipment.<br />

13. Ambient temperature above minimum.<br />

14. Fill and venting.<br />

15. Time at pressure.<br />

16. Visual inspection for leaks.<br />

17. Tightening of leaking mechanical or flange joints.<br />

18. Flush and water disposal.<br />

19. Dry and clean pipe.<br />

20. System and valve alignment returned to specified condition.<br />

B. Pneumatic Test Piping (typically Small Bore -- 2 inch and smaller -- and below 150 psi)<br />

1. Verify component pressure rating.<br />