Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

C. Strobe signal output and flash rate shall meet UL 1971 and ADAAG requirements. Unit<br />

shall have a xenon flash tube enclosed in a clear Lexan lens with “FIRE” in white<br />

lettering, and shall produce a synchronized strobe flash. Provide strobes with flash<br />

output levels as required to meet NFPA 72 visual signal requirements for each space.<br />

D. Horn/strobe shall mount to a 4” x 2-1/8” deep electrical box with single device cover.<br />

Provide weatherproof wall boxes for outdoor mounting.<br />

E. Manufacturers: Wheelock “HS” series, NO SUBSTITUTIONS.<br />

2.11 NOTIFICATION BOOSTER POWER SUPPLIES<br />

A. Provide notification circuit booster power supplies (as needed) that are acceptable to the<br />

FCP manufacturer and are compatible with the FCP.<br />

B. Manufacturers: FIRELITE “FCPS-24FS6” NO SUBSTITUTIONS.<br />

2.12 CONDUIT<br />

A. Install fire alarm wiring in intermediate metal conduit, rigid galvanized steel conduit, or<br />

electrical metallic tubing. Minimum conduit size 3/4 inch.<br />

B. Refer to Section 26 0533, Raceway and Boxes for Electrical Systems, for conduit<br />

systems.<br />

2.13 JUNCTION BOXES<br />

A. Refer to Section 26 0533, Raceway and Boxes for Electrical Systems, for junction boxes.<br />

2.14 WIR<strong>IN</strong>G<br />

A. Color Code: Use the following color code for the fire alarm system wiring:<br />

1. Black - 120-Volt AC phase wire.<br />

2. White - 120-Volt AC neutral wire.<br />

3. Green - System ground wire.<br />

4. Brown - Negative connection for strobe device. (If wired separately from horns.)<br />

5. Orange - Positive connection for strobe device. (If wired separately from horns.)<br />

6. Blue - Negative connection for horn circuit or horn/strobe combination circuit.<br />

7. Yellow - Positive connection for horn circuit or horn/strobe combination circuit.<br />

8. Gray - Negative conventional alarm initiating device connection.<br />

9. Violet - Positive conventional alarm initiating device connection.<br />

10. Black - Negative circuit connection for duct smoke detector reset, HVAC<br />

interlock, and other auxiliary connections.<br />

11. Red - Positive circuit connection for duct smoke detector reset, HVAC interlock,<br />

and other auxiliary connections.<br />

12. Black/Red Twisted Pair - Addressable device data loop, evacuation speaker<br />

circuit.<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 283100 - 11