Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

I. Full-Capacity Voltage Taps: Four 2.5 percent taps, 2 above and 2 below rated high voltage;<br />

with externally operable tap changer for de-energized use and with position indicator and<br />

padlock hasp.<br />

J. High-Voltage Switch: 200 A, make-and-latch rating of 10-kA RMS, symmetrical, arranged for<br />

loop feed with 3-phase, 4-position, gang-operated, load-break switch that is oil immersed in<br />

transformer tank with hook-stick operating handle in primary compartment.<br />

K. Primary Fuses: 150-kV fuse assembly with fuses complying with IEEE C37.47.<br />

1. Provide Bay-O-Net oil-immersed expulsion fuses in series with oil-immersed currentlimiting<br />

fuses. The Bay-O-Net expulsion fuses shall be RTE Bay-O-Net fuse catalog<br />

numbers 4000353C** or 4038108C** or equivalent. The current-limiting fuses shall be<br />

RTE ELSP, or equivalent, and shall be coordinated with the Bay-O-Net fuses to protect<br />

the transformer from faults beyond their interrupting rating. In order to eliminate or<br />

minimize oil spills, the bayonet fuse assembly shall include an oil retention valve inside<br />

the housing, which closes when the fuse holder is removed and an external drip shield.<br />

Warning shall be conspicuously displayed within the high-voltage compartment<br />

cautioning against removing or inserting fuses unless the load-break switch is in the open<br />

position and the tank pressure has been released.<br />

L. Surge Arresters: Rated 18 kV, fully shielded, dead-front, metal-oxide-varister, elbow type with<br />

resistance-graded gap, suitable for plugging into inserts. Provide three arresters for each<br />

transformer provided.<br />

M. High-Voltage Terminations and Equipment: Dead front with six high-voltage bushing wells for<br />

dead-front bushing-well inserts, complying with IEEE 386 and including the following:<br />

1. Bushing-Well Inserts: 200 amperes, 15 kV Class, one for each high-voltage bushing<br />

well.<br />

2. Surge Arresters: Dead-front, elbow-type, metal-oxide-varistor units.<br />

3. Parking Stands: One for each high-voltage bushing well.<br />

4. Portable Insulated Bushings: Arranged for parking insulated, high-voltage, load-break<br />

cable terminators; one for each primary feeder conductor terminating at transformer.<br />

5. Loop feed switch handle.<br />

6. Tap changer handle.<br />

7. Ground pads.<br />

N. Low-Voltage Terminations and Equipment: Low-voltage compartment shall contain lowvoltage<br />

bushings, with staggered NEMA spade terminals, as outlined in IEEE C57.12.34,<br />

Section 9.7.3, including a fully insulated Xo bushing (with removable ground strap),<br />

Accessories, and ground pads.<br />

O. Accessories:<br />

1. Drain Valve: 1 inch globe valve in secondary compartment to serve as oil drain valve,<br />

bottom filter press connection, and equipped with sampling valve located on the side of<br />

the drain valve.<br />

2. One-inch globe valve to serve as top filter press connection & vacuum pump connection.<br />

3. Externally mounted dial-type thermometer.<br />

4. Liquid-level gage.<br />

Contract 44577 KW Annex – Rev. D 44577-CSI-SPEC-001 261200 - 4