Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

<strong>SECTION</strong> 221413 - FACILITY STORM DRA<strong>IN</strong>AGE PIP<strong>IN</strong>G (FIRE WATER DRA<strong>IN</strong>AGE)<br />

PART 1 - GENERAL<br />

1.1 RELATED DOCUMENTS<br />

A. Drawings and general provisions of the Contract, including General and Supplementary<br />

Conditions and Division 01 Specification Sections, apply to this Section.<br />

1.2 SUMMARY<br />

A. This Section includes the fire water piping for the building:<br />

1. Pipe, tube, and fittings.<br />

2. Special pipe fittings.<br />

3. Hose.<br />

4. Fire Water Floor drains.<br />

5. Ball Valves.<br />

6. Single-Flange Butterfly valves.<br />

7. Encasement for underground metal piping.<br />

B. Related Sections include the following:<br />

1. Division 22 Section "Sanitary Sewerage Pumps (Fire Water Drainage Lift Station)."<br />

1.3 DEF<strong>IN</strong>ITIONS<br />

A. EPDM: Ethylene propylene diene monomer rubber.<br />

B. LLDPE: Linear, low-density polyethylene plastic.<br />

C. PE: Polyethylene plastic.<br />

D. PVC: Polyvinyl chloride plastic.<br />

E. SBR: Styrene-butadiene rubber.<br />

F. TPE: Thermoplastic elastomer.<br />

1.4 PERFORMANCE REQUIREMENTS<br />

A. Components and installation shall be capable of withstanding the following minimum workingpressure,<br />

unless otherwise indicated:<br />

1. Fire water Piping: 10-foot head of water.<br />

2. Fire water, Force-Main Piping: 50 psig.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 221413 - 1