Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

B. Design Pressure Rating: 160 psig.<br />

C. Safety Relief Valve Setting: 100 psig.<br />

D. Entering-Water Temperature: 105 deg F.<br />

E. Leaving-Water Temperature: 120 deg F.<br />

F. Design Water Flow Rate: 58 gpm.<br />

G. Design Pressure Drop: 5.0 ft water column.<br />

H. Output Capacity: 120 kW.<br />

I. Electrical Characteristics:<br />

1. kilowatts: 120<br />

2. Volts: 480 V.<br />

3. Phase: Three.<br />

4. Hertz: 60.<br />

2.7 SOURCE QUALITY CONTROL<br />

A. Test and inspect factory-assembled boilers, before shipping, according to ASME Boiler and<br />

Pressure Vessel Code.<br />

B. Hydrostatic Test: Factory test assembled boiler including hydrostatic test.<br />

C. Allow Owner access to source quality-control testing of boilers. Notify Engineer 14 days in<br />

advance of testing.<br />

PART 3 - EXECUTION<br />

3.1 EXAM<strong>IN</strong>ATION<br />

A. Before boiler installation, examine roughing-in for anchor-bolt sizes and locations, and piping<br />

and electrical connections to verify actual locations, sizes, and other conditions affecting boiler<br />

performance, maintenance, and operations.<br />

1. Final boiler locations indicated on Drawings are approximate. Determine exact locations<br />

before roughing-in for piping and electrical connections.<br />

B. Examine mechanical spaces, including required space for element removal, for suitable<br />

conditions where boilers will be installed.<br />

C. Proceed with installation only after unsatisfactory conditions have been corrected.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 235213 - 5