Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

1. Clean metal duct systems using mechanical cleaning methods that extract contaminants<br />

from within duct systems and remove contaminants from building.<br />

2. Use vacuum-collection devices that are operated continuously during cleaning. Connect<br />

vacuum device to downstream end of duct sections so areas being cleaned are under<br />

negative pressure.<br />

3. Use mechanical agitation to dislodge debris adhered to interior duct surfaces without<br />

damaging integrity of metal ducts, duct liner, or duct accessories.<br />

4. Clean coils and coil drain pans according to NADCA 1992. Keep drain pan operational.<br />

Rinse coils with clean water to remove latent residues and cleaning materials; comb and<br />

straighten fins.<br />

5. Provide drainage and cleanup for wash-down procedures.<br />

6. Antimicrobial Agents and Coatings: Apply EPA-registered antimicrobial agents if<br />

fungus is present. Apply antimicrobial agents according to manufacturer's written<br />

instructions after removal of surface deposits and debris.<br />

3.10 START UP<br />

A. Air Balance: Comply with requirements in Division 23 Section "Testing, Adjusting, and<br />

Balancing for HVAC."<br />

3.11 DUCT SCHEDULE<br />

A. Fabricate ducts with galvanized sheet steel except as otherwise indicated and as follows:<br />

1. Exhaust Ducts: stainless steel type 304 or 304L.<br />

B. Supply Ducts:<br />

1. Pressure Class: Positive 3-inch w.g.<br />

2. Minimum SMACNA Seal Class: A.<br />

3. SMACNA Leakage Class for Rectangular: 12.<br />

4. SMACNA Leakage Class for Round: 12.<br />

C. Return Ducts:<br />

1. Pressure Class: Negative 3-inch w.g.<br />

2. Minimum SMACNA Seal Class: A.<br />

3. SMACNA Leakage Class for Rectangular: 12.<br />

4. SMACNA Leakage Class for Round: 12.<br />

D. Exhaust Ducts:<br />

1. Fabrication pressure classification 20 inches w.g., negative pressure, Class 1.<br />

2. Normal operating pressure 10 inches w.g., negative pressure.<br />

3. Leak Test pressure 12.5 inches w.g., negative pressure.<br />

4. Structural Capability Test pressure 15 inches w.g., negative pressure.<br />

5. Seal duct seams and joints in accordance to the duct pressure classification as described<br />

in AG-1, Article SA-4300. All joints and seams shall be welded construction with<br />

flanged joints and gaskets and flanged joints and gaskets at connections to flanged<br />

equipment and dampers.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 233113 - 14