Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

3. 120V 20A.Control panel shall have a thermostatically controlled heater / fan.<br />

4. Heater package shall be Hoffman DAH1002A or approved equal.<br />

5. Main disconnect switch shall be UL98 listed and sized to handle full load amps of the<br />

panel, with pad-lockable door interlocking handle.<br />

6. UL 508e type combination starters (for 20HP and below) each with, IEC type<br />

combination starter<br />

7. Control power transformer with primary fuse protection,<br />

8. An HOA selector switch, RUN indicator, HIGH TEMPERATURE indicator, SEAL<br />

LEAK indicator and hour meter shall be provided for each pump. All pilot devices shall<br />

be UL Type 4X rated, 22mm type manufactured by Square D or equal. The indicators<br />

shall be long life LED type,<br />

9. An alarm horn shall be provided and mounted on the side of the panel. Horn shall be<br />

Federal Signal model 350 or equal with a minimum sound level of 100 db. A silence<br />

pushbutton shall be located on the inner door.<br />

10. An alarm light shall be mounted on the top of the panel, and shall be red polycarbonate<br />

and UL Type 4X rated.<br />

11. Control relays shall be provided as shown on plan drawings and shall be blade type, with<br />

indicator lights. Relays shall be IDEC or approved equal.<br />

12. Analog 4-20mA loops shall be provided with fuse protection.<br />

13. Intrinsically Safe Barriers provided for all control wiring such as Submersible<br />

Transducers, Floats and other low voltage devises.<br />

14. Inputs shall be provided for each pump to include moisture in motor, motor overtemperature,<br />

pump starter auxiliary contact to confirm pump operation when called,<br />

redundant high and low float switch and HOA Auto position to confirm the pump is<br />

available. Outputs shall be provided for each pump run command, out-of-service<br />

indicator for each pump, alarm horn, alarm dome light and general fault contact<br />

D. Sequence of Operation; Provide H-O-A selector switch. Inputs are provided and programmed<br />

into the DLC for a contact of the AUTO position of the selector switch. When the H-O-A is<br />

place into the HAND position, the DLC will be bypassed and the pump should run. If the<br />

contact to the H-O-A selector switch is in the OFF position and input of the DLC is not closed,<br />

the DLC sets the status of that pump to Out-Of-Service. When the H-O-A is placed into the<br />

AUTO position, the pump is available to run as instructed by the DLC. Touching the HAND,<br />

OFF or AUTO buttons on the Pump Status page will select the mode of operation. Touching the<br />

HAND button will start the pump in manual mode. The pumps are available for automatic run<br />

when the AUTO selector switch input is enabled and the “soft” H-O-A is in the AUTO mode.<br />

1. The analog level signal is converted to tenths of feet and that value is compared to the<br />

start and stop set points that are entered into the system by the user. On rising level, when<br />

the level is equal to or greater than the lead pump start set point, the lead pump will start.<br />

If the level continues to rise beyond the start lag pump set point, the lag pump will start.<br />

If there are more than two pumps, rising level will start the additional pumps in sequence.<br />

On falling level, the pumps will sequence off as the level drops below the respective stop<br />

set points.<br />

2. The pump alternation mode is set by the user. Automatic, time clock and manual modes<br />

are available.<br />

3. Automatic mode—the pumps will alternate after each pumping cycle.<br />

Time clock—the pumps will alternate daily at the time set by the user.<br />

Manual—the pumps will not alternate. The lead pump is selected by the user.<br />

Contract 44577 KW Annex – Rev. E 44577-CSI-SPEC-001 221329-5