Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

19. Adequate safety devices and fault indicator shall be incorporated to shut down the<br />

compressor and require manual reset in the event of:<br />

a. Loss of Air Cooling<br />

b. High Lubricant Temperature<br />

c. High Air Temperature<br />

d. Low Lubricant Level<br />

e. Low Lubricant Pressure<br />

f. Temporary Loss of Power<br />

20. Air Compressor Assembly Instrumentation shall contain the following:<br />

a. Hour Meter<br />

b. Air Usage Indicator Calibrated in Percent of Load<br />

c. Lubricant Temperature Gauge (Discharge From Compressor)<br />

d. Air Pressure Gauges.<br />

e. Air Filter Condition Indication<br />

f. Lubricant Filter Condition Indication<br />

g. Separator Element Condition Indicator<br />

h. Lubricant Reservoir Level Gauge<br />

21. Wet air receiver tank: 200 gallon, 200-psig rated horizontal steel tank with ASME safety<br />

valve, minimum pressure valve, blowdown valve, and suitable for supporting air<br />

compressor package.<br />

22. The compressor unit shall include all items not mentioned above that are normally supplied<br />

on a standard unit to assure proper operation of the unit. This shall include, but not be<br />

limited to, interconnecting piping and wiring, initial lubricant supply, steel base with all<br />

equipment mounted. All electrical components shall comply with the NEC.<br />

2.3 DRY AIR RECEIVERS<br />

A. Description:<br />

1. ASME Section VIII, Div. 1 coded pressure vessel.<br />

2. Arrangement: Vertical, 36-in. diameter by 124-in. tall.<br />

3. Capacity: 500 gal.<br />

4. Pressure Rating: 165 psig minimum.<br />

5. Safety Relief Valve Setting: 150 psig.<br />

6. Pressure gauge, 0-200 PSIG, with 4" face.<br />

7. Two 2-in FNPT ports.<br />

8. One 3-in FNPT port.<br />

9. 1-in. FNPT drain port.<br />

10. 1/2-in. FNPT top port.<br />

11. 1-1/2-in. FNPT port.<br />

12. Drain: Automatic electric valve with ½” manual isolation valve.<br />

13. Interior Finish: unpainted.<br />

14. Exterior finish: steel primer.<br />

15. Two each lifting lugs welded to top head.<br />

16. Standard bottom skirt and floor mount clip assembly (4 each)<br />

17. Auxiliary parts shipped loose.<br />

18. Assembly drawing and ASME Code data report.<br />