Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

b. CWP Rating: 200 psig.<br />

c. Body Design: Lug type; suitable for bidirectional dead-end service at rated<br />

pressure without use of downstream flange.<br />

d. Body Material: ASTM A 126, cast iron or ASTM A 536, ductile iron.<br />

e. Seat: EPDM.<br />

f. Stem: One- or two-piece stainless steel.<br />

g. Disc: Aluminum bronze.<br />

2.11 ENCASEMENT FOR UNDERGROUND METAL PIP<strong>IN</strong>G<br />

A. Description: ASTM A 674 or AWWA C105, high-density, crosslaminated PE film of 0.004inch<br />

or LLDPE film of 0.008-inch minimum thickness.<br />

B. Form: Sheet or tube.<br />

C. Color: Black or natural.<br />

PART 3 - EXECUTION<br />

3.1 EXCAVATION<br />

A. Refer to Division 31 Section "Earth Moving" for excavating, trenching, and backfilling.<br />

3.2 PIP<strong>IN</strong>G APPLICATIONS<br />

A. Flanges and unions may be used on aboveground pressure piping, unless otherwise indicated.<br />

B. Underground fire water drainage piping (gravity) NPS 6 and smaller shall be the following:<br />

1. Solid-wall Schedule 40 PVC pipe, PVC socket fittings, and solvent-cemented joints.<br />

C. Underground, fire water drainage piping (gravity) NPS 8 and larger shall be the following:<br />

1. Solid-wall Schedule 40 PVC pipe, PVC socket fittings, and solvent-cemented joints.<br />

D. Aboveground fire water drainage force mains NPS 1-1/2 and NPS 2 shall be any of the<br />

following:<br />

1. Steel pipe, pressure fittings, and threaded joints.<br />

E. Aboveground fire water drainage force mains NPS 2-1/2 and NPS 6 shall be the following:<br />

1. Steel pipe, pressure fittings, and welded or threaded joints.<br />

F. Underground fire water drainage force mains NPS 4 and smaller shall be the following:<br />

1. Steel pipe, pressure fittings, and welded or threaded joints.<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 221413 - 7