Sludge Treatment Project Engineered Container Retrieval and Transfer System January 2012<br />

1.7 EXTRA MATERIALS<br />

A. Furnish extra materials that match products installed and that are packaged with protective<br />

covering for storage and identified with labels describing contents.<br />

1. Gaskets: One set for each access door.<br />

2. Fan Belts: One set for each air-handling unit fan.<br />

PART 2 - PRODUCTS<br />

2.1 MANUFACTURERS (ECRT-AHU-501)<br />

A. Basis-of-Design Product: Subject to compliance with requirements contained in Section<br />

012513, Product Substitution Procedures, provide product indicated on Drawings or<br />

comparable product by one of the following:<br />

1. Carrier Corporation; a member of the United Technologies Corporation Family.<br />

2. McQuay International as the basis of design<br />

3. Miller-Pickering<br />

4. Temtrol<br />

5. Trane; American Standard Inc.<br />

2.2 UNIT CAS<strong>IN</strong>GS<br />

A. General Fabrication Requirements for Casings:<br />

1. Forming: Form walls, roofs, and floors with at least two breaks at each joint, minimum<br />

2” thick double wall assembly.<br />

2. Casing Joints: Sheet metal screws or pop rivets.<br />

3. Sealing: Seal all joints with water-resistant sealant.<br />

4. The inner and outer panels shall be fabricated of G90 Galvanized-Steel Casings minimum<br />

18 gauge.<br />

5. Airstream Surfaces: Surfaces in contact with the airstream shall comply with<br />

requirements in ASHRAE 62.1-2004.<br />

6. Fabricate unit with 16 gauge channel posts with panels secured with mechanical<br />

fasteners.<br />

7. All panels, access doors, and shipping sections shall be sealed with permanently applied<br />

bulb-type gasket.<br />

B. Casing Insulation and Adhesive:<br />

1. Materials: Minimum R-13, injected foam insulation or ASTM C 1071, Type II.<br />

Insulation shall carry a 25/50 rating for flame spread/smoke developed per ASTM E-84,<br />

UL723, and NFPA-90.<br />

2. Location and Application: Encased between outside and inside casing.<br />

C. Inspection and Access Panels and Access Doors:<br />

Contract 44577 KW Annex - Rev. E 44577-CSI-SPEC-001 237313 - 3