Sludge Treatment Project Engineered Container Retrieval and Transfer System December 2011<br />

Hardware Points Software Points<br />

Point Name AI AO BI BO AV BV Sched Trend Alarm Show On Graphic<br />

Fan Status × ×<br />

Fan Start/Stop × × ×<br />

Environmental Index × ×<br />

Percent of Time Satisfied × ×<br />

Schedule ×<br />

Heating Setpoint × ×<br />

Cooling Setpoint × ×<br />

High Zone Temp ×<br />

Low Zone Temp ×<br />

Filter Change Required ×<br />

Fan Failure ×<br />

Fan in Hand ×<br />

Fan Runtime Exceeded ×<br />

Totals 3 1 2 1 2 0 1 9 6 9<br />

1.9 ECRT-AHU-504<br />

Total Hardware ( 7 ) Total Software ( 18 )<br />

A. Run Conditions - Scheduled:<br />

1. The unit shall run according to a user definable time schedule in the following modes:<br />

2. Occupied Mode: The unit shall maintain<br />

a. A 80°F (adj.) cooling setpoint<br />

b. A 65°F (adj.) heating setpoint.<br />

B. Alarms shall be provided as follows:<br />

1. High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user<br />

definable amount (adj.).<br />

2. Low Zone Temp: If the zone temperature is less than the heating setpoint by a user<br />

definable amount (adj.).<br />

C. Zone Setpoint Adjust:<br />

1. The occupant shall be able to adjust the zone temperature heating and cooling setpoints at<br />

the zone sensor.<br />

D. Fan:<br />

1. The fan shall run anytime the unit is commanded to run, unless shutdown on safeties.<br />

E. Coil Valve:<br />

1. The controller shall measure the zone temperature and modulate the coil valve to<br />

maintain its heating or cooling setpoint.<br />

Contract 44577 KW Annex - Rev. D 44577-CSI-SPEC-001 230993 - 11