Option 7 - 24HR Alarm<br />

• Enabled the zone type will generate a 24HR alarm if the zone generates an alarm. The area state will not<br />

affect the generation of this alarm.<br />

• Disabled the zone type operates normally.<br />

Option 8 - Fire Alarm<br />

• Enabled the zone type will generate a fire alarm when it is activated. This zone type will also operate similar<br />

to the 24HR Alarm option.<br />

Most smoke detectors use a normally open contact so any zone that is assigned this option must have the<br />

inverted state option selected and the EOL resistors option enabled.<br />

• Disabled the zone type operates normally.<br />

Zone Type Report Options<br />

Reporting options for the zone type configure the operation of the zone type when reporting to a communication<br />

service and includes options for various other zone type options.<br />

ZT001 Report<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 - Report Alarm<br />

• Enabled the zone type will generate a reportable alarm message.<br />

• Disabled the zone type does not generate a reportable alarm message.<br />

Option 2 - Report Tamper<br />

• Enabled the zone type will generate a reportable tamper message.<br />

• Disabled the zone type does not generate a reportable tamper message.<br />

Option 3 - Report Bypass<br />

• Enabled the zone type will generate a reportable bypass message.<br />

• Disabled the zone type does not generate a reportable bypass message.<br />

Option 4 - Report Restore<br />

• Enabled the zone type will generate a reportable restore message.<br />

• Disabled the zone type does not generate a reportable restore message.<br />

Option 5 - Stay Zone<br />

• Enabled the zone type will generate an alarm if the area is armed in stay mode. The zone will stay armed.<br />

For zones that will be active when an area is armed in stay mode it is recommended to disable the event log<br />

for the zone.<br />

• Disabled the zone type operates normally.<br />

Option 6 - Force Zone<br />

• Enabled the zone type will allow the zones it is assigned to be force armed.<br />

• Disabled the zone type operates normally.<br />

Option 7 - No Exit Test<br />

• Enabled the zone type will not verify the status of a zone prior to the area starting to arm. Use this feature to<br />

assign zones in exit locations to prevent the area from generating a zone open warning when being armed.<br />

• Disabled the zone type operates normally.<br />

104 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE