Door Control Mode<br />

The control mode selects how the door will be controlled in the control door or control door group setting. This<br />

allows a door to be unlocked for the door unlock time, unlock latched or unlocked in the fire alarm mode.<br />

FN001 Door Mode<br />

Menu Timed<br />

Use the [1] and [3] keys to scroll the door control mode until you reach the setting that you want to use and then<br />

press [ENTER] to proceed to the next programmable option for the door control function. For more<br />

information about the list control data entry refer to the section List Control Data Entry (see page 344).<br />

Door Mode<br />

Menu Timed<br />

Menu Latched<br />

Fire Control<br />

Lockdown<br />

Lockdown (Entry<br />

Allowed)<br />

Lockdown (Exit<br />

Allowed)<br />

Lockdown (Entry and<br />

Exit Allowed)<br />

Description<br />

The Door will be unlocked for the door unlock time that is programmed for the door.<br />

Use this mode when you want to unlock the door for unlock time. The door will lock<br />

after the unlock time has expired.<br />

The door will be latched in the unlocked state and will remain unlocked until controlled<br />

from:<br />

A LCD Keypad<br />

<strong>Protege</strong> <strong>System</strong> Management Suite<br />

Scheduled Action<br />

Area Status<br />

A Programmable function.<br />

The door will be latched in the fire control unlock state and will remain unlocked until<br />

controlled from:<br />

A LCD Keypad<br />

<strong>Protege</strong> <strong>System</strong> Management Suite<br />

A Programmable function that is programmed to deactivate the fire alarm control.<br />

Door Lockdown will be started for the door or door group and will remain <strong>Protege</strong> an<br />

LCD Keypad or when the PGM input goes off if the function is operating in a Test and<br />

Follow mode.<br />

Door Lockdown with Entry Allowed will be started for the door or door group and will<br />

remain locked down until it is cancelled from the <strong>Protege</strong> <strong>System</strong> Management Suite,<br />

an LCD Keypad or when the PGM input goes off if the function is operating in a Test<br />

and Follow mode.<br />

Door Lockdown with Exit Allowed will be started for the door or door group and will<br />

remain locked down until it is cancelled from the <strong>Protege</strong> <strong>System</strong> Management Suite,<br />

an LCD Keypad or when the PGM input goes off if the function is operating in a Test<br />

and Follow mode.<br />

Door Lockdown with Entry and Exit Allowed will be started for the door or door group<br />

and will remain locked down until it is cancelled from the <strong>Protege</strong> <strong>System</strong> Management<br />

Suite, an LCD Keypad or when the PGM input goes off if the function is operating in a<br />

Test and Follow mode.<br />

Virtual Door Function<br />

To program the virtual door function ensure that the function you have selected is halted. Select the function<br />

type selection screen as shown below for the Virtual Door.<br />

FN001 Func Type<br />

Virtual Door<br />

Use the [1] and [3] keys to scroll the function types until you reach the door control selection and press [ENTER]<br />

to select the function type displayed and proceed to the next programmable option for the door control function.<br />

For more information about the list control data entry refer to the section List Control Data Entry (see page 344).<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 245

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!