Reporting Protocol<br />

The reporting protocol defines how the IP communication data will be sent to the monitoring station. Various<br />

protocols are supported to allow the most comprehensive solution.<br />

SV001 Format<br />

Armor IP<br />

Use the [1] and [3] keys to scroll the different protocols and press [ENTER] to select the protocol displayed. For<br />

more information about the list control data entry refer to the section List Control Data Entry (see page 344).<br />

Protocol<br />

Armor IP (UDP)<br />

Armor IP-E (UDP)<br />

Armor IP (TCP)<br />

Armor IP-E (TCP)<br />

CID Over IP<br />

SIA Over IP<br />

AlarmNZ IP<br />

Patriot LS30<br />

Function<br />

Armor IP will communicate to the Armor IP server software running on a remotely<br />

connected server at a central monitoring station using UDP transport. Please consult<br />

with the Monitoring station for transport layer and port details.<br />

Armor IP will communicate to the Armor IP server software running on a remotely<br />

connected server at a central monitoring station using UDP transport and NIST certified<br />

AES encryption. Please consult with the Monitoring station for transport layer, port and<br />

encryption key details.<br />

Armor IP will communicate to the Armor IP server software running on a remotely<br />

connected server at a central monitoring station using TCP transport. Please consult<br />

with the Monitoring station for transport layer and port requirements.<br />

Armor IP will communicate to the Armor IP server software running on a remotely<br />

connected server at a central monitoring station using TCP transport and NIST certified<br />

AES encryption. Please consult with the Monitoring station for transport layer, port and<br />

encryption key details.<br />

CID Over IP communicates a Contact ID message using the SIA DC09 specification<br />

format to any receiver that supports the SIA DC09 specification. SIA DC09<br />

Specification is currently not released as a formal specification and is subject to<br />

change.<br />

SIA Over IP communicates a SIA Level 2 message using the SIA DC09 specification<br />

format to any receiver that supports the SIA DC09 specification. SIA DC09<br />

Specification is currently not released as a formal specification and is subject to<br />

change.<br />

AlarmNZ IP is the IP Communication format used by Alarm New Zealand Limited. By<br />

default the AlarmNZ IP service will use the Contact ID reporting format. Information is<br />

sent using a login and password and then event information in a ASCII comma<br />

separated data format.<br />

Patriot LS30 Protocol is the IP Communication format used by Patriot <strong>System</strong>s central<br />

station automation application. By default the Patriot LS30 service will use a form of<br />

Contact ID reporting. Information is sent using a proprietary format and to obtain details<br />

the user should contact Patriot <strong>System</strong>s directly.<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 193