Analog Expander Channel 1 Options<br />

The channel one options configures the first channel on the Analog Expander. Please not that the settings may<br />

not relate to the particular device connected. Some options relate to the PRT-DAC4 Analog Output Expander<br />

and others to PRT-ADC4 Analog Input Expander.<br />

i<br />

The channel options require a module init or module init with reboot to take affect with the exception<br />

of the Log Channel Data Option 7, which is a controller based configuration setting.<br />

AE001 Ch 1 Opts<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 – Enable Channel Operation<br />

• Enabled the analog expansion device will process messages according to the options configuration and<br />

module type.<br />

• Disabled the channel will perform no function.<br />

Option 2 – Channel Input Output Configuration<br />

• When the option is enabled the input or output will operate in Current Mode and use the 0-20mA and<br />

4-20mA interface.<br />

• Disabled the channel will operate in 0-10V input or output mode.<br />

Option 3 – Preset PRT-DAC4 Output on Power Up<br />

• Enabled and the analog expansion module is a DAC module the output will be preset when it powers up to<br />

the setting in option 4.<br />

• Disabled the DAC output will be set to the last known value that it received.<br />

Option 4 – Set to Full Scale Output<br />

• Enabled and option 3 enabled the DAC output will be set to the maximum or full scale deflection.<br />

• Disabled and option 3 enabled the DAC will output a analog value of 0 on the voltage or current outputs.<br />

Option 5 – Reserved<br />

• Reserved do not modify<br />

Option 6 – Differentiate On Send Operation<br />

• Enabled the Analog Input channel will constantly monitor the analog input value for any variance greater<br />

than the configured differentiate value set for the channel and then send an update to the system controller.<br />

• Disabled the Input Channel will be sent based on the period configured in the channel time setting.<br />

Option 7 – Log Raw Analog Data<br />

• Enabled the Analog Expander channels when updated either as an input or an output will trigger a log in the<br />

event screen with the exact raw value. This is ideal for fault finding HOWEVER should not be left on in a live<br />

system as it will fill the event review rapidly.<br />

i<br />

To log data from a channel for charting and display purposes utilize the log option for variables in the<br />

<strong>Protege</strong> <strong>System</strong> Management Suite.<br />

• Disabled the data is not logged to the review screen.<br />

Option 8 - Reserved<br />

• Reserved do not modify<br />

Enabling/disabling or modifying the settings of reserved options is not recommended.<br />

88 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE