24HR Disabling<br />

The <strong>Protege</strong> <strong>System</strong> continually checks zones and trouble zones for a tamper condition regardless of the armed<br />

status of the area. The 24Hr processing monitors trouble zones as well as tamper and shorts on zones within<br />

the selected area. This allows the tamper zones to generate an alarm even if the area is disarmed. To disable<br />

the 24Hr processing of an area, you must have access to the area and the user must have the option to access<br />

the 24Hr Processing enabled.<br />

• Access the area status display screen as explained in section Area Status Display (see page 15). Using the<br />

scroll keys [ ] select the area that you want to disarm.<br />

*Area 001<br />

is DISARMED<br />

• From the Area Status screen, press the [] key to select the 24Hr Status screen.<br />

*Area 001<br />

24HR Enabled<br />

• From the Area 24Hr Status screen, press the [DISARM] key to disarm/disable the 24Hr processing in the<br />

selected area. Pressing the [DISARM] key starts the disable/disarming process.<br />

*Area 001<br />

24HR Busy<br />

• When the 24Hr disable/disarming process is completed the 24Hr area status will change to "24Hr<br />

Disabled".<br />

*Area 001<br />

24HR Disabled<br />

• Press the [] key to return to the area status display.<br />

• Press the [CLEAR] key to exit.<br />

i<br />

To disarm the 24Hr processing of the selected area, you must be able to access it, refer to the Area<br />

Security (see page 16). The user must have the access 24Hr Processing Option enabled.<br />

The <strong>Protege</strong> <strong>System</strong> protects the area programming by preventing ANY programming to be done<br />

when either the Area or the 24Hr processing of an area is enabled. You must always disable the 24Hr<br />

processing and disarm an area before the area can be programmed.<br />

Area Group Arming<br />

Area group processing allows you to arm or disarm a group of areas rather than one area at a time. The area<br />

group controlled is the area group assigned to the keypad used to access the system. To arm the area group<br />

the user must be able to access ALL the areas in the area group. The user must have the access area group<br />

option enabled to access the area group function.<br />

• Access the area status display screen as explained in section Area Status Display (see page 15).<br />

*Area 001<br />

is DISARMED<br />

• From the Area Status screen, press the [] key to select the Area group control screen.<br />

Press [ARM] or<br />

[DISARM] to<br />

The screen will scroll between the screen above and below prompting the user to press the [ARM] or<br />

[DISARM] key to control the area group that is shown.<br />

control group<br />

*Area Group 001<br />

• From the Area Group Control screen, press the [ARM] key to arm the selected area group. Pressing the<br />

[ARM] key starts the arming process for each area in the area group.<br />

• When the area group arming process is completed the display will return to the area group control screen.<br />

• Press the [] key to return to the area status display.<br />

• Press the [CLEAR] key to exit or the [MENU] key to select another menu option or function.<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 19