Use the [1] and [3] keys to scroll the available operating modes and press [ENTER] to select the operating mode<br />

displayed. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Primary IP Address<br />

The primary IP address is the IP of the device to which the BACnet service will communicate.<br />

SV001 Pri IP<br />

000.000.000.000<br />

To modify the IP address use the keypad as explained in section Entering Decimal Numbers (see page 341).<br />

Press [ENTER] to save the Octet that is being entered and move to the next Octet or the next screen once all<br />

four have been completed.<br />

Primary Port<br />

The primary port configures the TCP/IP port through which the BACnet communications will operate.<br />

SV001 Primary<br />

port: 47808<br />

To modify the port configuration use the keypad as explained in section Entering Decimal Numbers (see page<br />

341) and press [ENTER] to save the modified data.<br />

Device ID<br />

Enter the Device ID for the BACnet service.<br />

SV005 Device<br />

04444<br />

To modify the device ID use the keypad as explained in section Entering Decimal Numbers (see page 341) and<br />

press [ENTER] to save the modified data.<br />

Start PGM<br />

This is the first PGM in a range of PGMs to which the BACnet binary values are mapped.<br />

SV005 Start PGM<br />

no: 00000<br />

To modify the start PGM number use the keypad as explained in section Entering Decimal Numbers (see page<br />

341) and press [ENTER] to save the modified data.<br />

Total Number of PGMs<br />

Enter the total number of PGMs (in a contiguous range) that will be mapped to BACnet binary values.<br />

SV005 total PGM<br />

no: 00008<br />

To modify the total number of PGS setting use the keypad as explained in section Entering Decimal Numbers<br />

(see page 341) and press [ENTER] to save the modified data.<br />

202 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE