Intercom High Level Interface<br />

To program the Intercom High Level Interface service ensure that the service that has been selected is halted.<br />

Press the [ENTER] key until the display shows the service type selection screen.<br />

SV001 Ser Type<br />

Intercom<br />

Use the [1] and [3] keys to scroll the service types until you reach the Intercom selection and press [ENTER]. For<br />

more information about the list control data entry refer to the section List Control Data Entry (see page 344).<br />

Service Mode<br />

The service mode determines how this service operates with the system controller. By default a service is set to<br />

start with the operating system. Setting a service to "Start With The Operating <strong>System</strong>" (Start With O/S) allows<br />

the service to operate automatically, if the system controller is reset or restarts. <strong>Manual</strong> control of the service<br />

can be set by using the <strong>Manual</strong> option for the service mode.<br />

SV001 Ser Mode<br />

Start with O/S<br />

Use the [1] and [3] keys to scroll the available operating modes and press [ENTER] to select the operating mode<br />

displayed. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Intercom Type<br />

The Intercom Type selects the intercom that will be connected to the Serial Communications Interface.<br />

SV001 Intercom<br />

Siedle<br />

Use the [1] and [3] keys to scroll the different intercom types and press [ENTER] to select the intercom<br />

displayed. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Validation Mode<br />

Siedle<br />

Sentex Infinity<br />

Sentex Type L<br />

Enterphone<br />

Function<br />

Select when connecting the Siedle range of intercoms. Integrates to the Bus Control<br />

module by using an ACC-485 unit and appropriate RS232 cable to the PRT-COMM<br />

serial interface.<br />

Select when connecting to the Sentex Infinity Multiple Point intercoms from<br />

Chamberlain group. Connects to the serial RS232 output of the intercom, may need a<br />

suitable RS485 converter for distances above 15 meters.<br />

Select when connecting to the Sentex Type L single channel intercoms from<br />

Chamberlain group. Connects to the serial RS232 output of the intercom, may need a<br />

suitable RS485 converter for distances above 15 meters.<br />

Select when connecting to the Enterphone intercom system. Connects to the serial<br />

RS232 output of the intercom, may need a suitable RS485 converter for distances<br />

above 15 meters. The Enterphone unit does not support multi units and therefore does<br />

not need to have the intercom address set.<br />

186 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE