<strong>System</strong> <strong>Controller</strong> Restart in Bios Mode<br />

On the <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong>, Ensure Dip switch 2 is ON<br />

Cycle the power to the Module.<br />

To access the system controller restart menu select [MENU, 4, 9, 4]. The screen will immediately prompt<br />

"Press [ENTER] to restart panel".<br />

Pressing the [ENTER] key will restart the panel in bios mode, which allows firmware updates to be performed.<br />

The keypad that is currently being used will be restarted and will go offline for a short period of time while the<br />

panel restarts. This is part of normal operation for a panel restart.<br />

Press [ENTER] to<br />

restart panel.<br />

If a panel restart is not required press the [MENU] key to exit and remain logged in or press the [CLEAR] key to<br />

exit and logout.<br />

Custom Reader Format<br />

The <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> and <strong>Protege</strong> Reader Expansion Modules can support custom Wiegand Card<br />

Reader formats for the times when the format required is not one of the many available preset formats.<br />

One custom format can be added per controller and used by any reader expander in the system.<br />

Interface Type<br />

To access the custom reader format programming login using a valid installer code and then select [MENU, 4,<br />

9, 5]. The screen displays the first entry to modify as there is only one panel no record selection is required. The<br />

first item that is programmable is the output format.<br />

The data can either be output as Wiegand (D0 and D1) or Magnetic Data (Clock and Data).<br />

CF001 Type<br />

Wiegand<br />

Use the [1] and [3] keys to scroll the format type until you reach the required format and press [ENTER] to<br />

proceed. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Data Length<br />

The data length defines the total number of bits that are sent by the card reader for each card badge.<br />

CF001 Length<br />

bits: 026<br />

To modify the length (000 to 255), use the keypad as explained in section Entering Decimal Numbers (see page<br />

341) and press [ENTER].<br />

Facility Code Start<br />

The facility code start defines the index where the facility code data starts in the data transmitted. The count<br />

starts at zero.<br />

CF001 Site Start<br />

bits: 001<br />

To modify this parameter (000 to 255), use the keypad as explained in section Entering Decimal Numbers (see<br />

page 341) and press [ENTER].<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 269