20.01.2015 Views

Protege System Controller Reference Manual

Protege System Controller Reference Manual

Protege System Controller Reference Manual

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Function Mode<br />

The function mode determines how this function operates with the system controller. By default a function is set<br />

to normal operation. Normal operation will mean the function is started if it was running when the system<br />

restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will<br />

allow the function to run once and then wait to be stopped and started by the user or operator. Setting the run<br />

once option for the RTHP will result in NO operation being performed and the function stopping a short time<br />

after it is started.<br />

FN001 Func Mode<br />

Normal<br />

Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to<br />

proceed to the next programmable option for the floor temping function. For more information about the list<br />

control data entry refer to the section List Control Data Entry (see page 344).<br />

Enabled Control PGM<br />

Enabled Control PGM is set when the Floor Temping is to run and will operate only when the enabled PGM is<br />

on. If no enabled PGM is set the Floor Temping will run continuously. Programming a PGM that is activated by a<br />

schedule allows the floor temping to operate only during the times that the space is occupied.<br />

FN001 Enabled<br />

pgm: --000:00<br />

To modify the enable PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

Fault PGM<br />

The fault control PGM is set when a fault condition has occurred and the Floor Temping is to shutdown. This<br />

allows the Floor Temping to shutdown in the shortest possible time without causing any damage to the system.<br />

In the case of a fire shutdown the system must have a fire PGM programmed.<br />

FN001 Fault<br />

pgm: --000:00<br />

To modify the fault PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

Fire PGM<br />

The fire control PGM is monitored NOT controlled by the function and when the fire PGM has been activated,<br />

typically by an external fire alarm input, the floor tempering will gracefully shut down the system and halt<br />

operation until the fire alarm has been cleared. This PGM could be the PGM used to deactivate smoke dampers<br />

and other related equipment in the HVAC control system.<br />

FN001 Fire<br />

pgm: --000:00<br />

To modify the fire PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345). Do not set a PGM group for the fire or other monitored PGM's as this will have no action in the control<br />

system and will be the same as not setting a PGM value.<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 233

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!