Link Me (IO)<br />

The Link Me (IO) Service provides an interface for <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong>s to communicate together through<br />

the linking of PGM outputs. This service maps PGMs on one <strong>System</strong> <strong>Controller</strong> to a second <strong>System</strong> <strong>Controller</strong><br />

so they follow the state of the primary <strong>System</strong> <strong>Controller</strong>.<br />

To program the Link Me Service ensure that the service that has been selected is halted. Press the [ENTER] key<br />

until the display shows the service type selection screen.<br />

SV001 Ser Type<br />

Link Me (IO)<br />

Use the [1] and [3] keys to scroll the service types until you reach the Link Me selection and press [ENTER]. For<br />

more information about the list control data entry refer to the section List Control Data Entry (see page 344).<br />

Service Mode<br />

The service mode determines how this service operates with the system controller. By default a service is set to<br />

start with the operating system. Setting a service to "Start With The Operating <strong>System</strong>" (Start With O/S) allows<br />

the service to operate automatically, if the system controller is reset or restarts. <strong>Manual</strong> control of the service<br />

can be set by using the <strong>Manual</strong> option for the service mode.<br />

SV001 Ser Mode<br />

Start with O/S<br />

Use the [1] and [3] keys to scroll the available operating modes and press [ENTER] to select the operating mode<br />

displayed. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Primary IP Address<br />

The primary IP address is the IP of the <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> that is being linked with.<br />

SV001 Pri IP<br />

000.000.000.000<br />

To modify the IP address use the keypad as explained in section Entering Decimal Numbers (see page 341).<br />

Press [ENTER] to save the Octet that is being entered and move to the next Octet or the next screen once all<br />

four have been completed.<br />

Primary Port<br />

The primary port configures the TCP/IP port the two <strong>System</strong> <strong>Controller</strong>s will communicate over.<br />

SV001 Primary<br />

port: 09647<br />

To modify the port configuration use the keypad as explained in section Entering Decimal Numbers (see page<br />

341) and Press [ENTER] to save the modified data.<br />

Polling Time<br />

The polling time is set to schedule periodic connections with the other system controller.<br />

SV001 Poll<br />

time: 120 secs<br />

Edit the polling time to a value of 10 to 255 seconds, any number below 10 will disable the polling being sent to<br />

the controller. Use the keypad as explained in section Entering Decimal Numbers (see page 341) and press<br />

[ENTER].<br />