Option 8 - Recycle Zone On Exit Delay<br />

• Enabled the zone type will recheck the zones it is assigned when the area completes the exit delay cycle<br />

and if a zone is open recycle the zone to force it in to generating an alarm.<br />

Use this feature for a zone type used on a zone that may be breached during the exit delay such as a<br />

window or door contact.<br />

• Disabled the zone type operates normally.<br />

Zone Type Miscellaneous Options<br />

Miscellaneous options for the zone type configure options for various functions.<br />

ZT001 Misc<br />

[1-3-----]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 - Generate Siren Bell Output<br />

• Enabled the zone type will activate the siren bell output programmed for the area.<br />

• Disabled the zone type will not generate a bell output.<br />

Option 2 - Restart Siren Bell Timer<br />

• Enabled the zone type will restart the bell timer on each subsequent alarm.<br />

• Disabled the zone type will not alter the bell timer if it is already active.<br />

Option 3 - Save Alarm to Memory<br />

• Enabled the zone type will save an alarm message to the area's alarm memory storage area.<br />

• Disabled the zone type does not save an alarm message.<br />

Option 4 - Disarm Control Area on Restore<br />

• Enabled the zone type will disarm the control area when a zone assigned the zone type restores from an<br />

alarm condition.<br />

Use this feature and the arming control area feature as a on and off key switch arming input.<br />

• Disabled the zone type takes no action on the control area.<br />

Option 5 - Arm Control Area on Alarm<br />

• Enabled the zone type will start arming the control area when a zone assigned the zone type generates an<br />

alarm condition.<br />

• Disabled the zone type takes no action on the control area.<br />

Option 6 - Toggle Control Area State On Alarm<br />

• Enabled the zone type will toggle the state of the control area when the zone that is assigned this zone type<br />

generates an alarm.<br />

• Disabled the zone type operates normally.<br />

Option 7 - Force Arm Tamper<br />

• Enabled the zone type will allow the zone to be force armed if the zone assigned the zone type is tampered.<br />

• Disabled the zone type operates normally.<br />

Option 8 - Activate Entry PGM For Bell Siren Time Duration<br />

• Enabled the zone type will activate the entry PGM programmed for the area for the duration of the bell siren<br />

time.<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 105