Enabled Control PGM<br />

Enabled Control PGM is set when the RTHP is to run and will operate only when the enabled PGM is on. If no<br />

enabled PGM is set the RTHP will run continuously. This allows the RTHP to operate only during the times that<br />

the space is occupied. The signal can also be a memory register or a Boolean (bit) value from the selected<br />

memory register.<br />

FN001 Enabled<br />

pgm: --000:00<br />

To modify the occupy PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

Fault PGM<br />

The fault control PGM is set when a fault condition has occurred and the RTHP is to shutdown. This allows the<br />

RTHP to shutdown in the shortest possible time without causing any damage to the system. In the case of a fire<br />

shutdown the system must have a fire PGM programmed.<br />

FN001 Fault<br />

pgm: --000:00<br />

To modify the fault PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345). To select a data register press the stay key, the following screen will be shown and a memory register<br />

location can be selected. To view the memory register locations refer to appendix memory registers.<br />

Fire PGM<br />

The fire control PGM is monitored NOT controlled by the function and when the fire PGM has been activated,<br />

typically by an external fire alarm input, the RTHP will gracefully shut down the air conditioning system and halt<br />

operation until the fire alarm has been cleared. This PGM could be the PGM used to deactivate smoke dampers<br />

and other related equipment in the HVAC control system.<br />

FN001 Fire<br />

pgm: --000:00<br />

To modify the fire PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345). Do not set a PGM group for the fire or other monitored PGM's as this will have no action in the control<br />

system and will be the same as not setting a PGM value.<br />

Fan Control PGM<br />

The fan PGM is activated when the RTHP starts to operate and is started 30 seconds prior to any heating,<br />

cooling or dehumidification is required allowing it to ramp up to the desired speed.<br />

FN001 Fan<br />

pgm: --000:00<br />

To modify the fan PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />