Average<br />

The average function takes the average of up to eight input registers and writes this to an output register.<br />

To program the Average function ensure that the function you have selected is halted. Select the function type<br />

selection screen as shown below for the Average function.<br />

FN001 Fnc Type<br />

Average<br />

Use the [1] and [3] keys to scroll the function types until you reach the desired function and press [ENTER] to<br />

select this and proceed to the next programmable option. For more information about the list control data entry<br />

refer to the section List Control Data Entry (see page 344).<br />

Function Mode<br />

The function mode determines how this function operates with the system controller. By default a function is set<br />

to normal operation. Normal operation will mean the function is started if it was running when the system<br />

restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will<br />

allow the function to run once and then wait to be stopped and started by the user or operator.<br />

FN001 Fnc Mode<br />

Normal<br />

Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to<br />

proceed to the next programmable option for the Average function. For more information about the list control<br />

data entry refer to the section List Control Data Entry (see page 344).<br />

Input Registers<br />

Select up to eight Input registers. If a valid register number is entered it will be used as part of the Average<br />

calculation. If an invalid register number is selected (eg. 65535) then it will not be used as part of the calculation.<br />

FN001 Input #1<br />

reg: 00001<br />

...<br />

FN001 Input #8<br />

reg: 65535<br />

To modify the Input registers (00000 to 65535), use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER].<br />

Output Register<br />

Select a register to which the output will be written.<br />

FN001 Output<br />

reg: 65535<br />

To modify the Output register (00000 to 65535), use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER].<br />

Update Time<br />

Select an Update time. This is the number of seconds between the update of the output register.<br />

FN001 Update<br />

time: 00005 secs<br />

To modify the Update time (00001 to 65535 seconds), use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER].<br />