Register Offset<br />

Register Function<br />

9 Cooling Stage Off<br />

Cooling stages are being turned off progressively due to the set point being reached.<br />

10 Dehumidification Cooling Plus Reheat<br />

Dehumidification is required and the current set point is above the cooling set point. The<br />

dehumidification stage will be entered in an attempt to get the humidity under control.<br />

11 Dehumidification Transition<br />

The dehumidification process is in a transition between the dehumidification<br />

requirements and cooling.<br />

12 Dehumidification Heating<br />

Dehumidification is required and the current set point is below the heating set point. The<br />

dehumidification stage will be entered in an attempt to get the humidity under control<br />

while an attempt is also made to obtain heating set point.<br />

13 Dehumidification Heating Stage Off<br />

Dehumidification and heating stages are deactivated because the humidity has come<br />

under control or the cooling set point (other side of the dead band setting) has been<br />

reached.<br />

14 Dehumidification Cooling Stage Off<br />

Dehumidification and cooling stages are deactivated because the humidity has come<br />

under control or the heating set point (other side of the dead band setting) has been<br />

reached.<br />

15 Dehumidification Stage Off<br />

16 RTHP Shutting Down<br />

17 Fault Condition<br />

18 Fire Condition<br />

Dehumidification stages are deactivated because the humidity has reached set point and<br />

dehumidification is no longer required.<br />

The RTHP is completing an orderly shutdown of the currently activated stages and the<br />

fan control signals.<br />

A fault condition has activated that has caused the RTHP to shut down. This condition is<br />

typical of a smoke damper closing or other mechanical input that will result in the RTHP<br />

shutting down.<br />

A fire alarm condition has been activated that has caused the RTHP to shut down.<br />

Space Temperature Register<br />

The space temperature register is the register that is updated by an analogue module input channel connected<br />

to a temperature sensor. The space temperature is typically from a sensor located within the space the RTHP is<br />

controlling.<br />

FN001 Space temp<br />

reg: 00000<br />

To modify the space temperature register (00000 to 65535, use the keypad as explained in section Entering<br />

Decimal Numbers (see page 341) and press [ENTER].<br />

i<br />

If you are unsure how the RTHP operates and what action is going to be started as a result in the<br />

change in the input registers you can specify the register to be a normal register outside the analogue<br />

module range. This will allow an installer to modify the values with the <strong>Protege</strong> <strong>System</strong> Management<br />

Suite and visually see the mode change in the RTHP without the need to physically connect the RTHP.<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 231