Reader Port 2 Keypad Operation Mode<br />

The keypad operation mode programmed for the reader on port two determines if the reader port has a pin<br />

entry device attached or uses a local LCD keypad.<br />

RD001 R2 Key Mod<br />

None<br />

Use the [1] and [3] keys to scroll the available keypad mode settings. For more information about the list control<br />

data entry refer to the section List Control Data Entry (see page 344).<br />

i<br />

When a Wiegand 26 Bit Keypad is used PIN numbers that are prefixed with a 0 can not be used and<br />

the maximum pin number is limited to 65533. This is a limitation of the 26 Bit Format and not the<br />

Reader Expander. To utilize the full 8 digit capacity for the PIN number of a user and allow prefixed<br />

PIN numbers select a PIN device that supports the ARK-501 or 4 Bit Output Formats.<br />

Reader Port 2 LCD Keypad<br />

If the keypad operation mode is set to use one of the selected LCD keypads you can program the address of<br />

the keypad to use for pin entry. When using this mode of operation the LCD keypad will present a login<br />

message when a valid card is presented that requires pin entry.<br />

RD001 R2 Keypad<br />

None<br />

Use the [1] and [3] keys to scroll the available keypad mode settings. For more information about the list control<br />

data entry refer to the section List Control Data Entry (see page 344).<br />

Reader Port 2 Multi Badge Operation<br />

The reader port can perform various operations when a user badges their card multiple times. The list below<br />

details the modes this can operate in.<br />

When a multi badge operation has taken place the reader expander will beep the buzzer output four times. In<br />

area control, if the area is already armed the reader will only beep twice.<br />

RD001 R2 Badge<br />

None<br />

Use the [1] and [3] keys to scroll the available arming operation settings. For more information about the list<br />

control data entry refer to the section List Control Data Entry (see page 344).<br />

Mode<br />

None<br />

Arm on 2 Reads<br />

Arm on Card Read and<br />

Zone Input 8<br />

Arm on 3 Reads<br />

Toggle Function PGM<br />

Activate Function PGM<br />

Operation<br />

No action will be taken by the system for arming an area associated with the door.<br />

Two successive reads from the same user will result in the inside or outside area<br />

(depending on the card reader type configuration) starting the arming process.<br />

Pressing and holding Zone Input 8 (RDXXX:08) while presenting a card will begin<br />

arming. Zone 8 must be in an area that is armed to ensure the zone information is<br />

transmitted to the system controller. The area armed will depend on the card<br />

reader type setting.<br />

Three successive reads from the same user will result in the inside or outside area<br />

(depending on the card reader type configuration) starting the arming process.<br />

Three successive reads from the same user will result in the function PGM state<br />

being toggled. If the PGM is currently on it will be turned off and if it is off it will be<br />

turned on.<br />

Three successive reads from the same user will result in the function PGM state<br />

being turned on<br />