Area<br />

An installation may contain any number of areas or partitions depending on the configuration and size of the<br />

system needed. Areas can contain zones and trouble zones that protect the area. Zones can be assigned to as<br />

many as four areas and perform a different function in each area individually of the other area's status.<br />

Any area may also contain no zones and be used to control lighting, car parking, user loiter functions, automatic<br />

teller machines, banking and money trail control. The area processing is a powerful solution and one of key<br />

features of the <strong>Protege</strong> <strong>System</strong>.<br />

To access the area programming menu, login using a valid installer code that is allowed area menu access and<br />

then select [MENU, 4, 4]. The Areas menu enables you to set up and program all the areas in your system. This<br />

includes setting entry and exit delays and special options for each area.<br />

Areas can only be programmed when they are disarmed and the 24hr (Tamper) processing has been disabled,<br />

for information on controlling the area refer to the Area Control Section (see page 16). If the area is armed or the<br />

24hr processing is enabled, you can only view the screens, but not modify them.<br />

Selecting an Area to Modify<br />

Each area is assigned a unique area number from 001 to 250. Your system will be limited to specific number of<br />

areas that are defined in the selected profile. For information on profiles refer to the Advanced Programming<br />

Section (see page 207).<br />

Select area to<br />

modify: AR001<br />

Type the appropriate 3-digit area number or use the [] and [] keys to scroll the available area numbers.<br />

When the desired area number appears on the screen, press [ENTER] to program the selected area number.<br />

The maximum number of areas that can be programmed is limited by your system's memory and configured<br />

profile.<br />

Area Name<br />

If the selected area has a name associated (some areas do not have a name associated with them) the name<br />

programming screen will be shown.<br />

AR001 Name<br />

*Area 001<br />

To scroll areas by name use the [] and [] keys. To modify or enter a new name for the selected area use the<br />

keypad as explained in section Entering Text and Names (see page 341) and press [ENTER].<br />

By default the area name will be prefixed by an '*' this indicates that the name is an editable name in the<br />

system. Some areas do not have names, this is limited by the system memory and the profile configured.<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 113