20.01.2015 Views

Protege System Controller Reference Manual

Protege System Controller Reference Manual

Protege System Controller Reference Manual

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Option 7 - Log Operating <strong>System</strong> Assertion Events<br />

• Enabled the system controller will log operating system assertion events that occur. An assertion event is<br />

generating when the system controller gets a value, command or performs a function that results in a<br />

condition that is not deemed normal.<br />

• Disabled the system controller will not log operating system assertion events.<br />

Option 8 - Remote Login Not Required<br />

• Enabled the system controller will not validate the login and user name that is provided from the remote<br />

<strong>Protege</strong> <strong>System</strong> Management Suite or other remote host systems that must log in to the system.<br />

• Disabled the system controller will require that any external host accessing the system uses a valid login and<br />

user id number to gain access.<br />

Enabling/disabling or modifying the settings of reserved options is not recommended.<br />

Miscellaneous Options<br />

Miscellaneous options include configuration settings that affect the offline functions and remote intelligent door<br />

reader operations.<br />

Misc Options<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 – Auto Update Offline Users<br />

• Enabled the system controller will automatically update offline configuration parameters to all RDI modules<br />

at the time programmed in the Offline User Update Time.<br />

• Disabled the system controller will take no action for offline users.<br />

Option 2 – Use Alternate Resistors<br />

• Enabled the system controller will use alternate EOL configured resistors (2K2 and 6K8).<br />

• Disabled the system controller will use the normal 1K and 1K resistor configuration.<br />

Option 3 – Invert Module Tamper<br />

• Enabled the system controller will invert the module tamper input allowing a normally open (door closed)<br />

tamper switch to be used.<br />

• Disabled the system controller will use the standard normally closed (door closed) tamper switch.<br />

Option 4 - Reserved<br />

• Reserved do not modify<br />

Option 5 - Reset Anti-Passback Status On schedule<br />

The anti-passback status of all users can be reset on schedule. This flag will enable this global function. The<br />

associated 'Anti-Passback reset schedule' must also be set correctly for this option to function.<br />

Option 6 - Enable Timed User Anti-Passback Reset<br />

A specific time for Entry and Exit anti-passback can be set under the Door options to block a user from passing<br />

through a door too often. The time can be individually specified per Door but is globally enabled using this<br />

option flag.<br />

Enabling/disabling or modifying the settings of reserved options is not recommended.<br />