Zone Number Contact ID Code Reporting Point Number<br />

| | | | | | | |<br />

RD016:16 143 (Module Offline) 932<br />

RD017:01 145 (Module Tamper) 999<br />

| | | | | | | |<br />

RD250:16 143 (Module Offline) 999<br />

In the above table a reporting code of 999 indicates that the trouble zone is outside the maximum trouble zones<br />

that can be reported for the module type.<br />

16 PGM Output Expander<br />

The 16 PGM output expander will report trouble zones from 1 to 8 on the first 4 modules, all modules above<br />

address PX004 will be reported using the default code of 999.<br />

Zone Number Contact ID Code Reporting Point Number<br />

PX001:01 145 (Module Tamper) 933<br />

PX001:02 301 (AC Loss) 934<br />

PX001:03 302 (Low <strong>System</strong> Battery) 935<br />

PX001:04 312 (Auxiliary Fuse) 936<br />

PX001:05 312 (Relay Supply off / Fire Input off) 937<br />

PX001:06 140 (General Alarm) 938<br />

PX001:07 140 (General Alarm) 939<br />

PX001:08 143 (Module Offline) 940<br />

PX002:01 145 (Module Tamper) 941<br />

| | | | | | | |<br />

PX004:08 143 (Module Offline) 964<br />

PX005:01 145 (Module Tamper) 999<br />

| | | | | | | |<br />

PX250:16 143 (Module Offline) 999<br />

In the above table a reporting code of 999 indicates that the trouble zone is outside the maximum trouble zones<br />

that can be reported for the module type.<br />

Analog Input/Output Expander<br />

The Analog expander will report trouble zones from 1 to 8 on the first 2 modules, all modules above address<br />

AE002 will be reported using the default code of 999.<br />

Zone Number Contact ID Code Reporting Point Number<br />

AE001:01 145 (Module Tamper) 965<br />

AE001:02 312 (Analog Voltage Low) 966<br />

AE001:03 312 (Auxiliary Fuse) 967<br />

AE001:04 140 (General Alarm) 968<br />