Zone<br />

Number<br />

Alarm<br />

Code<br />

Restore<br />

Code<br />

CP001:28 YC YK 28 Service 1 Fault 5028<br />

CP001:29 YC YK 29 Service 2 Fault 5029<br />

CP001:30 YC YK 30 Service 3 Fault 5030<br />

CP001:31 YC YK 31 Service 4 Fault 5031<br />

CP001:32 UA UH 5032<br />

| | | | | | |<br />

CP001:64 UA UH 5064<br />

Keypad Trouble Zones<br />

Reporting<br />

Point Number<br />

The keypad will report trouble zones from 1 to 8 on the first 128 modules, all modules above address KP128 will<br />

be reported using the default code of 9999.<br />

Zone<br />

Number<br />

Alarm<br />

Code<br />

Restore<br />

Code<br />

KP001:01 TA TH 01 Tamper 5065<br />

KP001:02 UA UH 02 Power 5066<br />

KP001:03 PA PH 03 Panic 5067<br />

KP001:04 HA HH 04 Duress 5068<br />

KP001:05 DH DR 05 Left Open 5069<br />

KP001:06 DF DR 06 Forced Open 5070<br />

KP001:07 JA UJ 07 Locked Out 5071<br />

KP001:08 EM EN 08 Communication 5072<br />

KP002:01 TA TH 01 Tamper 5073<br />

| | | | | | |<br />

KP128:08 EM EN 08 Communication 6088<br />

KP129:01 UA UH 9999<br />

| | | | | | |<br />

KP250:08 UA UH 9999<br />

Reporting<br />

Point Number<br />

In the above table a reporting code of 9999 indicates that the zone is outside the maximum zones that can be<br />

reported for the module type.<br />

16 Zone Expander Trouble Zones<br />

The 16 zone expander will report trouble zones from 1 to 16 on the first 32 modules, all modules above address<br />

ZX032 will be reported using the default code of 9999.<br />

Zone<br />

Number<br />

Alarm<br />

Code<br />

Restore<br />

Code<br />

ZX001:01 TA TH 01 Tamper 6089<br />

ZX001:02 AT AR 02 AC 6090<br />

Reporting<br />

Point Number<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 309