20.01.2015 Views

Protege System Controller Reference Manual

Protege System Controller Reference Manual

Protege System Controller Reference Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Enabled Control PGM<br />

Enabled Control PGM is set when the value compare function is to run and will operate only when the enabled<br />

PGM is on. If no enabled PGM is set the value compare function will run continuously. This allows the value<br />

compare function to operate only during the times that the resulting PGM is required.<br />

FN001 Enabled<br />

pgm: --000:00<br />

To modify the enabled PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

High PGM<br />

The High PGM output will activate when the input data register (usually an input from an analog register) is<br />

above the set point plus the hysterisis value and has been for the duration of the hysterisis time. The high PGM<br />

will turn off if the input value is below the set point value.<br />

FN001 High<br />

pgm: --000:00<br />

To modify the High PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

Low PGM<br />

The Low PGM output will activate when the input data register (usually an input from an analog register) is below<br />

the set point minus the hysterisis value and has been for the duration of the hysterisis time. The low PGM will<br />

turn off if the input value is above the set point value.<br />

FN001 Low<br />

pgm: --000:00<br />

To modify the low PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

Base Data Register<br />

The Base data register is used as the first register in the list of registers used to configure, program and control<br />

the Value Compare. The only registers that are not included in the base registers are ones that must link to an<br />

analog input or analog output for external sensors (Temp, Daylight (LUX), Water Level). A base data register<br />

setting MUST be set to ensure the system can pick up the set points and data values.<br />

FN001 Base data<br />

reg: 00000<br />

To modify the base data register (00000 to 65535, use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER].<br />

Base Data Register Offset<br />

Register Offset<br />

Register Function<br />

0 Input Value Set Point<br />

The input value set point is used to determine at what point the comparison input register<br />

value used in the calculation is high or low. The Input Hysterisis value is added or<br />

subtracted from the set point to prevent an oscillation on the output PGM's.<br />

238 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!