Communications Port Number<br />

The communications interface port defines which serial port the controller will use for communication with the<br />

Clipsal C-Bus PCI Interface. Select the communication port that will be plugged in to the PCI connection.<br />

SV001 Port<br />

Ext Port 1<br />

Use the [1] and [3] keys to scroll the communication ports and press [ENTER] to select the operating mode<br />

displayed. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Communications Port Speed<br />

The communications port speed defines the baud rate at which the Clipsal C-Bus service will operate. The<br />

default value for C-Bus is 9600 bits per second. If the speed or configuration is different adjust this setting to<br />

suit the C-Bus PCI configuration.<br />

SV001 Speed<br />

9600<br />

Use the [1] and [3] keys to scroll the communication port speed options and press [ENTER] to select the speed<br />

displayed. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Communications Port Parity<br />

The communications port parity defines the parity configuration for the communication with the C-Bus PCI. This<br />

will default to No Parity however this can be adjusted to suit the C-Bus PCI configuration.<br />

SV001 Parity<br />

No Parity<br />

Use the [1] and [3] keys to scroll the communication parity options and press [ENTER] to select the parity<br />

displayed. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

TCP/IP Primary IP Address<br />

If the port option 'Ethernet' was selected then you are given the option to enter the IP address of the CNI unit.<br />

SV005 Pri IP<br />

191.012.003.077<br />

To modify the IP address use the decimal entry from (000 to 255), use the keypad as explained in section<br />

Entering Decimal Numbers (see page 341) and press [ENTER].<br />

TCP/IP Primary Port<br />

If the port option 'Ethernet' was selected then you are given the option to enter the TCP/IP Port of the CNI unit.<br />

SV005 Primary<br />

port: 09999<br />

To modify the port number (00001 to 65534), use the keypad as explained in section Entering Decimal Numbers<br />

(see page 341) and press [ENTER].<br />

184 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE