Heating Stage 2 PGM<br />

The heat 2 PGM is activated when the RTHP has a requirement for heating and the heating stage demand value<br />

has been exceeded for the second stage. The heating 2 PGM will typically be used to control the second stage<br />

of the heating system.<br />

FN001 Heat 2<br />

pgm: --000:00<br />

To modify the heat 2 PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

Heating Stage 3 PGM<br />

The heat 3 PGM is activated when the RTHP has a requirement for heating and the heating stage demand value<br />

has been exceeded for the third stage. The heating 3 PGM will typically be used to control the third stage of the<br />

heating system.<br />

FN001 Heat 3<br />

pgm: --000:00<br />

To modify the heat 3 PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

Heating Stage 4 PGM<br />

The heat 4 PGM is activated when the RTHP has a requirement for heating and the heating stage demand value<br />

has been exceeded for the fourth stage. The heating 4 PGM will typically be used to control the fourth stage of<br />

the heating system.<br />

FN001 Heat 4<br />

pgm: --000:00<br />

To modify the heat 4 PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345).<br />

Dehumidification Stage 1 PGM<br />

The dehumidification stage 1 PGM is activated when the RTHP has a requirement for dehumidification. The<br />

dehumidification process will typically open the first stage of the hot gas reheat valves located in the RTHP unit.<br />

FN001 Dehumid 1<br />

pgm: --000:00<br />

To modify the dehumidification stage 1 PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups (see page 345).<br />

Dehumidification Stage 2 PGM<br />

The dehumidification stage 2 PGM is activated when the RTHP has a requirement for dehumidification and the<br />

humidity is above the hysteresis value plus the setpoint. The dehumidification process will typically open the<br />

second stage of hot gas reheat valves located in the RTHP unit.<br />

FN001 Dehumid 2<br />

pgm: --000:00<br />

To modify the dehumidification stage 2 PGM, use the settings as explained in section Entering PGM and PGM<br />

Groups (see page 345).<br />