Elevator Control<br />

To program the Elevator Control function ensure that the function you have selected is halted. Select the<br />

function type selection screen as shown below for Elevator Control.<br />

FN001 Func Type<br />

Elevator Ctrl<br />

Use the [1] and [3] keys to scroll the function types until you reach the door control selection and press [ENTER]<br />

to select the function type displayed and proceed to the next programmable option for the elevator control<br />

function. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Function Mode<br />

The function mode determines how this function operates with the system controller. By default a function is set<br />

to normal operation. Normal operation will mean the function is started if it was running when the system<br />

restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will<br />

allow the function to run once and then wait to be stopped and started by the user or operator.<br />

FN001 Func Mode<br />

Normal<br />

Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to<br />

proceed to the next programmable option for the elevator control function. For more information about the list<br />

control data entry refer to the section List Control Data Entry (see page 344).<br />

Elevator Action<br />

The action determines what action is performed on the elevator group that is programmed as a result of the<br />

Input PGM. An action MUST be selected for the programmable function to operate correctly.<br />

FN001 Action<br />

None<br />

Use the [1] and [3] keys to scroll the action types until you reach the required action that you want to be<br />

performed and then press [ENTER] to proceed to the next programmable option for the elevator control<br />

function. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

• Follow and Test<br />

The floor group status follows the programmed input one state and will retest the input state every 30<br />

second interval and change the floor group state accordingly.<br />

Input One<br />

ON<br />

OFF<br />

Floor Group<br />

UNLOCKED<br />

LOCKED<br />

Test Action - If the floor group state is changed externally or is part of another programmable function the<br />

programmable function will only restore the output state after 30 seconds has elapsed. This time is only<br />

used if the programmable function was NOT responsible for the change in state. If a door has a door unlock<br />

time and the door mode is set to timed this will unlock the door every 30 seconds.<br />

• Not Follow and Test<br />

Performs the same function as above however the output is inverted (NOT). This logic action is a test action,<br />

consult the follow and test action for an explanation of the Test Function.<br />

Input One<br />

ON<br />

OFF<br />

Output<br />

LOCKED<br />

UNLOCKED<br />

250 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE