Reader Port 2 Process Options<br />

Options that relate to the extra reader functions.<br />

RD001 R2 Process<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 – Convert Force to Door Open<br />

• Enabled the reader expander will process door forced open events as door open events.<br />

• Disabled the reader will process forced door events as normal.<br />

Option 2 – Disable Red LED Processing<br />

• Enabled the reader expander will not control the Red LED (L2) and the PGM can be used for another<br />

function, this is particularly useful if the attached proximity reader LED's is controlled with one wire.<br />

• Disabled the reader will turn on the Red LED when the door is locked.<br />

Option 3 – Disable Green LED Processing<br />

• Enabled the reader expander will not control the Green LED (L1) and the PGM can be used for another<br />

function, this is particularly useful if the attached proximity reader LED's is controlled with one wire.<br />

• Disabled the reader will turn on the Green LED when the door is unlocked.<br />

Option 4 – Disable Buzzer Processing<br />

• Enabled the reader expander will not control the Buzzer Output (BZ) and the PGM can be used for another<br />

function.<br />

• Disabled the reader will control the buzzer output.<br />

Option 5 - 8 - Reserved<br />

• Reserved do not modify<br />

Enabling/disabling or modifying the settings of reserved options is not recommended.<br />

Reader Port 2 Elevator Options<br />

Options that relate to the elevator functions.<br />

RD001 R2 Elv Opt<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 – Invert Floor Relays<br />

• Enabled the reader expander will invert all the relays on the PX16's connected that are used for elevator<br />

control.<br />

• Disabled the reader will not invert the relays.<br />

Option 2 – Control on Comm Fail<br />

• Enabled the PX16 used for elevator control will control the state of the relays when they go offline. Option<br />

3 determines the state the relays will go into.<br />

• Disabled the PX16 used for elevator control will not change the state of the relays when they go offline..<br />

Option 3 – Activate on Comm Fail<br />

• Enabled the PX16 will activate the relays when they go offline.<br />

• Disabled the PX16's will deactivate the relays when they go offline.<br />

84 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE