• Disabled the C-Bus processing will ignore any change from On to Off.<br />

Option 7 and 8 - Reserved<br />

• Reserved do not modify<br />

Enabling/disabling or modifying the settings of reserved options is not recommended.<br />

Panel Configuration<br />

The panel configuration allows hardware settings to be programmed in to the system controller that affect the<br />

way it operates and functions. To access the panel configuration programming login using a valid installer code<br />

and then select [MENU, 4, 9, 2]. The screen displays the first entry to modify as there is only one panel no<br />

record selection is required. The first item that is programmable is the AC Failure time as shown in the following<br />

example.<br />

AC Failure<br />

time: 030 secs<br />

Every time you press the Enter key, the next screen appears. The different screens are described in the<br />

following sub-sections. Programming the panel settings in the <strong>Protege</strong> <strong>System</strong> allow you to configure the<br />

hardware. Some settings that are programmable require that a service that uses the setting is restarted (for<br />

example changing the TCP/IP Address requires that the TCP/IP service is restarted).<br />

AC Failure Time<br />

The AC Failure time allows the installer to program a time that AC mains voltage must have failed before<br />

activating the AC Failure Trouble Zone. Set this to a larger value for locations that experience frequent but short<br />

interruptions in power or that operates on a generator frequently.<br />

AC Failure<br />

time: 030 secs<br />

To modify the AC Failure time (000 to 255 Seconds), use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER].<br />

AC Restore Time<br />

The AC Restore time allows the installer to program a time that AC must be present for after a AC Failure before<br />

restoring the AC Failure Trouble Zone. Set this to a larger value for locations that experience frequent but short<br />

interruptions in power or that operates on a generator frequently.<br />

AC Restore<br />

time: 030 secs<br />

To modify the AC Restore time (000 to 255 Seconds), use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER].<br />

Battery Test Time<br />

The battery test time allows the installer to program the duration of time in minutes between each battery test<br />

that is performed. A battery test is performed immediately on power up of the panel and then every<br />

programmed period. Each battery test takes 45 seconds and the battery low/failure trouble zone will activate if<br />

the battery fails.<br />

Battery Test<br />

Time: 015 mins<br />

To modify the Battery Test time (000 to 255 Minutes), use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER].<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 261