This allows the reader expander to monitor the reading device and generate a reader missing alarm (Trouble<br />

Zone) if it fails to communicate with the reader expander allowing the failure to be reported to a monitoring<br />

station.<br />

• Disabled the intelligent reader mode is disabled.<br />

Reader Port 2 Miscellaneous Options<br />

Options that relate to the miscellaneous reader functions.<br />

RD001 R2 Misc<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 - Disarm Area<br />

• Enabled the reader process will disarm the area designated by the reader type (ENTRY or EXIT) and the<br />

door configuration programmed (If it has an area on the inside or outside assigned).<br />

If this option is enabled and the reader is only used for area control then the area disarmed will be the area<br />

assigned in the area control setting.<br />

• Disabled the reader will not perform any disarm functions.<br />

Option 2 – Allow User Access if Area Armed<br />

• When the option is enabled the user will be granted access based on the access control configuration only<br />

and the area status will not be checked against the user's ability to disarm the area.<br />

• When the option is disabled and the user who is attempting access to a door that has an area assigned that<br />

is armed and the user can not disarm the area the user will be denied entry to the door even though they<br />

may have the correct door and schedule settings.<br />

Option 3 - Disarm User Area<br />

• Enabled the reader will disarm the user's area when access is granted to the door they are attempting to<br />

access. The users area must still be available in the user area group assigned to the users access level.<br />

• Disabled the reader will not perform any user area functions.<br />

Option 4 - Generate Reader Events<br />

• Enabled the reader events will be logged to the event review log.<br />

• Disabled the reader will not log the events to the event review log.<br />

Option 5 - Swap LED Lock Display<br />

• Enabled the LED display associated with the lock status will follow lock output one. Use this option when a<br />

reader expander is used in an ENTRY and EXIT configuration and only one lock output is controlling the<br />

door.<br />

• Disabled the lock and LED display is processed normally.<br />

Option 6 - Activate Access Level PGM<br />

• Enabled the reader expander will activate the PGM assigned to the users access level that gained access to<br />

the door or reader.<br />

The user must have the allow access level PGM option enabled.<br />

• Disabled the reader will not perform any action on the access level PGM.<br />

Option 7 - Display Card Data<br />

• Enabled the reader expander will display the actual card data received from the reader when the card<br />

number is not known. This can be used to interface with custom third party applications that require their<br />

own processing of card information.<br />

• Disabled the reader will display the card number not found message.<br />

82 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE