Register Offset<br />

Register Function<br />

19 Integral Calculation Time<br />

The integral calculation time is a time base used by the integral portion of the PI loop to<br />

update the Integral Error. It is advised not to set this below a value of 30 seconds.<br />

20 Fresh Air Damper Normal Setting<br />

The fresh air damper normal setting is the value that is output on the fresh air economies<br />

analog output used to control the fresh air damper position. This value allows the system<br />

to be tuned to an appropriate setting to allow the require Litres Per Second of fresh air to<br />

enter the RTHP.<br />

Roof Top Heat Pack Mode Definition<br />

Register Offset<br />

Register Function<br />

0 RTHP Idle Condition<br />

The programmable function is idle and no processing is taking place.<br />

1 RTHP Waiting For Start Signal<br />

The programmable function is waiting for the enable PGM signal to be controlled to an<br />

ON state to start operation. This is usually managed by a schedule or the alarm status.<br />

When the signal is received the Fan PGM will be activated and the programmable<br />

function will enter a delay of 30 seconds before starting.<br />

2 RTHP Warm Up Check<br />

If the RTHP is programmed to enter a warm up state at the start of operation the<br />

temperature will be checked here to verify if the warm up temperature is above the<br />

current space temperature if it is then the RTHP will enter the warm up mode.<br />

3 RTHP Warm Up Space<br />

When in warm up mode the RTHP is driven to full capacity to get the space above the<br />

heating set point in the fastest possible time. Once the temperature reaches this level the<br />

system will operate normally.<br />

4 RTHP Deadband Process<br />

The deadband process is where the RTHP will wait for a condition that is outside the set<br />

points for heating, cooling or dehumidification.<br />

5 On Call For Space Heating<br />

The space temperature is below the heating set point and the function to start the<br />

heating process is active. This will activate the stages required to bring the temperature<br />

up to the heating set point.<br />

6 On Call For Space Cooling<br />

The space temperature is above the cooling set point and the function to start the<br />

cooling process is active. This will activate the stages required to bring the temperature<br />

down to the cooling set point.<br />

7 On Call For Fresh Air Space Cooling<br />

8 Heating Stage Off<br />

The space temperature is above the cooling set point and the outside air is below the<br />

free air cooling set point, the RTHP will oscillate the fresh air economizer in attempt to<br />

cool the space using the fresh air intake. This will remain active until the temperature is<br />

below the cooling set point or if the free cooling fails to achieve set point in the set time<br />

(Free Cooling Time) mode 6 will be entered.<br />

Heating stages are being turned off progressively due to the set point being reached.<br />

230 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE