Keypad Offline Menu Options<br />

These options turn on or off the menus that are available when the keypad is logged out or offline. The keypad is<br />

logged out or offline when no valid user code (PIN) has been entered. It is important to note that even if a menu<br />

cannot be accessed online through this keypad (see menu groups); it is possible that it could still be accessed<br />

through the offline menu if the following options are turned on. In the same instance a user can be able to<br />

access a menu online but not offline.<br />

KP001 Offline<br />

[-2-4----]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 - Automation Menu<br />

• Enabled the keypad will allow access to the Automation Menu if no user is logged in and a user press's the<br />

[MENU] key.<br />

• Disabled the keypad will not allow access to the Automation Menu offline.<br />

Option 2 - View Trouble Menu<br />

• Enabled the keypad will allow access to the View Trouble Menu if no user is logged in and a user press's<br />

the [MENU] key.<br />

• Disabled the keypad will not allow access to the View Trouble Menu offline.<br />

Option 3 - Event Review Menu<br />

• Enabled the keypad will allow access to the Event Review Menu if no user is logged in and a user press's<br />

the [MENU] key.<br />

• Disabled the keypad will not allow access to the Event Review Menu offline.<br />

Option 4 - Keypad Information Menu<br />

• Enabled the keypad will allow access to the Keypad Information Menu if no user is logged in and a user<br />

press's the [MENU] key. It is recommended to leave this option enabled.<br />

• Disabled the keypad will not allow access to the Keypad Information Menu offline.<br />

Option 5, 6, 7 and 8 - Reserved<br />

• Reserved do not modify<br />

Enabling/disabling or modifying the settings of reserved options is not recommended.<br />

Zone Expander<br />

To access the Zone Expander module programming login using a valid installer code and then select [MENU, 4,<br />

1, 2]. The screen displays "Zone exp to modify" as shown in the following example.<br />

16 Zone Exp to<br />

modify: ZX001<br />

Every time you press the Enter key, the next screen appears. The different screens are described in the<br />

following sub-sections. Programming the Zone Expander allows you to set the polling time of the module and<br />

power supply options.<br />

When programming modules some options are processed at the module, for these options to operate correctly<br />

a network update must be performed and the zone expander must be registered and online.<br />

Updating modules can be accessed by selecting [MENU, 4, 8, 1, 3], you can also check the status of your<br />

modules by selecting [MENU, 4, 8, 1, 1] for all modules presently offline and [MENU, 4, 8, 1, 2] for all online<br />

modules. For more information refer to the Advanced menu section (see page 207).<br />