Option 2 - Door Open Event When On Schedule<br />

• Enabled the door will not log a door opened event when it is unlocked on schedule. This will prevent the<br />

door from filling the event buffer with events that are not needed.<br />

• Disabled the door will generate a door open and close.<br />

Option 3 - Generate Door Pre-Alarm Event<br />

• Enabled the door will generate a pre-alarm event when the pre-alarm timer for the door is reached.<br />

• Disabled no pre-alarm event will be generated.<br />

Option 4 - Generate Door Left Open Event<br />

• Enabled the door will generate a door left open event when the door maximum open time is reached.<br />

• Disabled no left open event will be generated.<br />

Option 5 - Relock Door When Closed<br />

• Enabled the door will lock when it detects a door close event and the lock output is activated.<br />

• Disabled the relock function will not control the door.<br />

Option 6 - Unlock Request To Exit (REX)<br />

• Enabled the door will activate the lock PGM when a request to exit occurs.<br />

• Disabled the door will not control the lock PGM.<br />

Option 7 - Unlock Request To Enter (REN)<br />

• Enabled the door will activate the lock when a request to enter occurs.<br />

• Disabled the door will not control the lock PGM.<br />

Option 8 - Late Open Schedule<br />

• Enabled the Door will not unlock on schedule until the first access has been accepted at the door.<br />

• Disabled the first user in will not prevent the schedule from operating and will activate the door if<br />

programmed normally.<br />

Special Options<br />

Special options for the door include the control of the door from the inside and outside areas.<br />

DR001 Special<br />

[--------]<br />

To modify options, use the keypad as explained in section Entering Data Options (see page 344).<br />

Option 1 - Door Lock Follows Inside Area<br />

• Enabled the door will unlock if the inside area is disarmed. If no arm/disarm schedule is set, Option 6 MUST<br />

be enabled for this function to operate.<br />

• Disabled the door will not unlock when the inside area is disarmed.<br />

Option 2 - Door Lock Follows Outside Area.<br />

• Enabled the door will unlock if the outside area is disarmed. If no arm/disarm schedule is set, Option 6<br />

MUST be enabled for this function to operate.<br />

• Disabled the door will not unlock when the outside area is disarmed.<br />

Option 3 - Prevent Slave Door Unlocking On Inside Area<br />

• Enabled the door will not activate the slave door if the inside area is armed.<br />

• Disabled the slave door will activate regardless of the inside area status.<br />

PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE 137