FN001 Comp inp<br />

reg: 00000<br />

To modify the comparison input register (00000 to 65535), use the keypad as explained in section Entering<br />

Decimal Numbers (see page 341) and press [ENTER].<br />

Ripple Control PGM Output Function<br />

The ripple control function will activate and then deactivate in sequence the PGM's that are assigned to the<br />

stage outputs. Ideally suited for staging on lighting and air conditioning systems in large industrial sites.<br />

FN001 Func Type<br />

Ripple PGM<br />

Use the [1] and [3] keys to scroll the function types until you reach the Ripple PGM selection and press [ENTER]<br />

to select the function type displayed and proceed to the next programmable option for the Value Compare<br />

function. For more information about the list control data entry refer to the section List Control Data Entry (see<br />

page 344).<br />

Function Mode<br />

The function mode determines how this function operates with the system controller. By default a function is set<br />

to normal operation. Normal operation will mean the function is started if it was running when the system<br />

restarts or is completely powered down (AC Failure and Battery Failure). The Run Once mode of operation will<br />

allow the function to run once and then wait to be stopped and started by the user or operator.<br />

i<br />

Setting the run once option for the ripple PGM function will result in NO operation being performed<br />

and the function stopping a short time after it is started.<br />

FN001 Func Mode<br />

Normal<br />

Use the [1] and [3] keys to scroll the function mode until you reach the normal selection and press [ENTER] to<br />

move to the next programmable option for the ripple PGM function. For more information about the list control<br />

data entry refer to the section List Control Data Entry (see page 344).<br />

Enabled Control PGM<br />

The Enabled Control PGM is used to operate the ripple PGM function in the STEP UP mode when it is activated<br />

and it will run in the STEP DOWN mode when the Enable PGM is deactivated. If no enabled PGM is set the<br />

function will never run the ripple stages.<br />

FN001 Enabled<br />

pgm: --000:00<br />

To modify the enabled PGM, use the settings as explained in section Entering PGM and PGM Groups (see page<br />

345). To select a data register press the stay key, the following screen will be shown and a memory register<br />

location can be selected. To view the memory register locations refer to appendix memory registers.<br />

Ripple On Time<br />

The ripple on time determines the time that each PGM output will be delayed before being activated when the<br />

ripple control function is stepping the PGM outputs up.<br />

FN001 Ripple on<br />

time: 00000 secs<br />

To modify the ripple on time (00000 to 65535 seconds), use the keypad as explained in section Entering<br />

Decimal Numbers (see page 341) and press [ENTER].<br />

240 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE