Reader Expander<br />

To access the Reader Expander module programming login using a valid installer code and then select [MENU,<br />

4, 1, 3]. The screen displays "Reader exp to modify" as shown in the following example.<br />

2 Reader Exp to<br />

modify: RD001<br />

Every time you press the Enter key, the next screen appears. The different screens are described in the<br />

following sub-sections. Programming the Reader Expander allows you to set the polling time of the module,<br />

power supply options and the configuration of the readers with associated doors.<br />

When programming modules some options are processed at the module, for these options to operate correctly<br />

a network update must be performed and the zone expander must be registered and online.<br />

Updating modules can be accessed by selecting [MENU, 4, 8, 1, 3], you can also check the status of your<br />

modules by selecting [MENU, 4, 8, 1, 1] for all modules presently offline and [MENU, 4, 8, 1, 2] for all online<br />

modules. For more information refer to the Advanced Menu section (see page 207).<br />

Selecting a Reader Expander to Modify<br />

Each Reader expander is assigned a unique address from 001 to 250. Programming the address of the Reader<br />

Expander Module (PRT-RDI2, PRT-RDM2, PRT-RDS2 and PRT-RDE2) is covered in the installation instructions<br />

included with your Reader Expander Module.<br />

2 Reader Exp to<br />

modify: RD001<br />

Type the appropriate 3-digit Reader Expander address or use the [] and [] keys. When the desired address<br />

appears on the screen, press [ENTER] to program the selected Reader Expander module. The maximum<br />

number of Reader Expanders that can be programmed is limited by your system's memory and configured<br />

profile.<br />

Displaying Selected 2 Reader Expander Information<br />

It is possible to show the current 2 Reader Expander registration and information details (registration, online and<br />

version) from the 2 Reader Expander selection display.<br />

2 Reader Exp to<br />

modify: RD001<br />

Type the appropriate 3-digit 2 Reader Expander address or use the [] and [] keys. When the desired<br />

address appears on the screen, press the [ARM] key to display information on the selected 2 Reader Expander.<br />

The screen will now display information about the 2 Reader Expander that was selected. Press any other key to<br />

return to the 2 Reader Expander selection window.<br />

11-14-72-B9 [23]<br />

V 1.31 2404 M RO<br />

The display above represents the following information for the selected keypad:<br />

11-14-72-B9<br />

Serial Number of the registered 2 Reader Expander at the selected address.<br />

[23] The current polling timeout value.<br />

V 1.05<br />

Software version of the registered keypad.<br />

2404 Software version build number.<br />

M<br />

R<br />

O<br />

This is the module type that is registered at this location.<br />

M - Mini 2 Reader Expander<br />

S - Standard 2 Reader Expander<br />

I - Intelligent 2 Reader Expander<br />

E - Ethernet 2 Reader Expander<br />

The 2 Reader expander is registered.<br />

('*' will indicate no expander registered)<br />

The 2 Reader expander is online.<br />

('*' will indicate the expander is offline)<br />