Space Humidity Register<br />

The space humidity register is the register that is updated by an analogue module input channel connected to a<br />

humidity sensor. The space humidity sensor is typically located within the space the RTHP is controlling at a<br />

height of 1.5 to 2.5 meters above floor level.<br />

FN001 Space rh<br />

reg: 00000<br />

To modify the space humidity register (00000 to 65535, use the keypad as explained in section Entering<br />

Decimal Numbers (see page 341) and press [ENTER].<br />

External Fresh Air Temperature Register<br />

The external fresh air temperature register is the register that is updated by an analogue module input channel<br />

connected to a temperature sensor. The external fresh air temperature is typically from a sensor located within<br />

fresh air intake of the RTHP in the cowling section. The fresh air temperature sensor is used to calculate the<br />

ability to cool the space with direct fresh air and is calculated prior to a demand for cooling.<br />

FN001 Fresh temp<br />

reg: 00000<br />

To modify the fresh temperature register (00000 to 65535, use the keypad as explained in section Entering<br />

Decimal Numbers (see page 341) and press [ENTER].<br />

Economiser Damper Register<br />

The Base data register is used as the first register in the list of registers used to configure, program and control<br />

the RTHP. The only registers that are not included in the base registers are ones that must link to an analog<br />

input or analog output for external sensors (Temp, Humidity or Dampers). A base data register setting MUST be<br />

set.<br />

FN001 Space rh<br />

reg: 00000<br />

To modify the base data register (00000 to 65535, use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER].<br />

Floor Tempering Control Function<br />

The Floor Tempering programmable function allows the direct control of a single stage floor tempering system<br />

that controls a duct mounted heater and/or cooling compressor. The support for one heating and one cooling<br />

state is provided as well as a forward and reverse operation.<br />

FN001 Func Type<br />

Floor Temping<br />

Use the [1] and [3] keys to scroll the function types until you reach the Floor Temping selection and press<br />

[ENTER] to select the function type displayed and proceed to the next programmable option for the Floor<br />

Temping control function. For more information about the list control data entry refer to the section List Control<br />

Data Entry (see page 344).<br />

232 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE