Option 3 - Multiple Reader Connected to Port 2<br />

• Enabled the reader will process the multiplexed reader inputs on Port 2 so that dual readers can be<br />

connected for entry and exit processing. The duplex reader that is connected will always operate as the exit<br />

reader.<br />

• Disabled the reader port 2 interface will operate as a single reader input.<br />

Option 4 – Use Alternate Resistors<br />

• Enabled the reader expander will use alternate EOL configured resistors (2K2 and 6K8).<br />

• Disabled the reader expander will use the normal 1K and 1K resistor configuration.<br />

Option 5 – Invert Module Tamper<br />

• Enabled the reader expander will invert the module tamper input allowing a normally open (door closed)<br />

tamper switch to be used.<br />

• Disabled the reader expander will use the standard normally closed (door closed) tamper switch.<br />

Option 6, 7 and 8 - Reserved<br />

• Reserved do not modify<br />

Enabling/disabling or modifying the settings of reserved options is not recommended.<br />

Reader Port 1 Mode<br />

The reader mode setting determines what function the reader attached to port one will perform.<br />

RD001 R1 Mode<br />

Access<br />

Use the [1] and [3] keys to scroll the reader mode settings. For more information about the list control data entry<br />

refer to the section List Control Data Entry (see page 344).<br />

Operating Mode<br />

Access<br />

Elevator<br />

Area Control<br />

Operation<br />

The reader expander port is used to control access through doors. You must<br />

configure the door that is controlled by this reader expander. This mode should also<br />

be used if control of a lobby or elevator call button is required. To control a elevator<br />

car use the Elevator Mode.<br />

The reader expander is used to control access to floors within an elevator. You must<br />

configure the elevator number that is connected to the reader.<br />

The reader expander input is used to ONLY control an area for arming and disarmed.<br />

Please note that this can be achieved using the Access Mode as well by integrating<br />

the alarm and access control systems.<br />

Reader Port 1 Controlled Door<br />

The reader controlled door setting sets the door that the reader on port one will provide card and control<br />

information to. It is possible that more than one reader has the same controlled door (Entry and Exit reading<br />

configuration).<br />

RD001 R1 Door<br />

*Door 001<br />

Use the [1] and [3] keys to scroll the available door settings. For more information about the list control data<br />

entry refer to the section List Control Data Entry (see page 344).<br />