Area Entry Delay Time<br />

Setting an entry delay time for the area allows users that have entered a secured point to have time to disarm<br />

the area before the area generates an alarm. Only zones that have a zone type assigned with an entry delay<br />

option set will start the entry delay timer for the area.<br />

AR001 Entry<br />

time: 060 secs<br />

To enter a entry delay time (000 to 250), use the keypad as explained in section Entering Decimal Numbers (see<br />

page 341) and press [ENTER].<br />

Area Exit Delay Time<br />

Setting an exit delay time for the area allows users to exit the area once the arming of the area has begun<br />

without triggering an alarm. Zones that are part of the exit route should be programmed with the exit option in<br />

the assigned zone type.<br />

AR001 Exit<br />

time: 030 secs<br />

To enter a exit delay time (000 to 250), use the keypad as explained in section Entering Decimal Numbers (see<br />

page 341) and press [ENTER]. An exit delay time of 000 seconds will result in the area arming instantly.<br />

Area Siren Bell Time<br />

The bell time determines how long the bell/siren output for the area will remain activated before timing out. If the<br />

option to retrigger the bell time is set in the zone type assigned to a zone that is triggered in the area the siren<br />

bell time is reloaded on each subsequent alarm activation.<br />

Use the siren bell time and the retrigger bell option from the zone type for smart automation of lighting and<br />

building control.<br />

AR001 Bell<br />

time: 004 mins<br />

To enter a bell siren time (000 to 250 minutes), use the keypad as explained in section Entering Decimal<br />

Numbers (see page 341) and press [ENTER]. A bell siren time of 000 will result in no siren or bell activation.<br />

Intelligent False Alarm Prevention Time<br />

Setting an intelligent false alarm prevention time allows the area to process alarms using smart alarm verification.<br />

For an alarm to occur in the area it will require that the same zone generate more than one alarm in a time<br />

programmed or that any other zone that is not assigned the intelligent false alarm prevention time generates an<br />

alarm.<br />

AR001 Intel zone<br />

time: 000 secs<br />

To enter an intelligent false alarm prevention time (000 to 250 seconds), use the keypad as explained in section<br />

Entering Decimal Numbers (see page 341) and press [ENTER]. Setting the intelligent false alarm prevention time<br />

to a value of 000 will result in any intelligent false alarm prevention zone from activating normally.<br />

114 PRT-CTRL-SE <strong>Protege</strong> <strong>System</strong> <strong>Controller</strong> <strong>Reference</strong> <strong>Manual</strong> | PRT-CTRL-SE